90
8. System
build-up
It is necessary to set as follows in order to make the controller communicate with the CC-Link Master (PLC)
and controller through the gateway unit.
[1] Controller setting for SIO communication (Modbus communication) between the gateway unit and
controller
[2] Setting of PLC side and gateway unit for CC-Link communication between the PLC and gateway unit
8.1. Communication setting for controller
It is necessary to set as follows in order to make the controller communicate with the gateway unit.
(1) Set so as not to duplicate axis No.
Note that a range of settable axis No. depends on the operation mode of the gateway unit.
(2) Parameter setting
[1] Set the parameter No. 16 “SIO communication speed” to “230400” (230.4 kbps).
SIO communication cannot be performed in a setting other than 230.4 kbps.
[2] Set the parameter No. 17 “Slave station transmitter activation minimum delay time” to “5” or less.
When attempting to execute the communication cycle at the fastest speed, set it to “0.”
Summary of Contents for RCM-GW-CC
Page 1: ...IAI America Inc CC Link RCM GW CC Gateway Unit Operation ManualFirst Edition...
Page 4: ......
Page 10: ...6 1 5 How to identify model RCM GW CC Basic model For CC Link Gateway unit...
Page 12: ...8 2 2 External dimension drawing Mounting dimension...
Page 78: ...74...
Page 82: ...78 Position data measurement value Present position 1 2 3 4 4 5 6 7...
Page 84: ...80 Speed acceleration and deceleration set value Actuator speed Speed n2 Speed n3 1 2 3...
Page 88: ...84 Command position No Completion position No 1 2 3 4 5 6...
Page 91: ...87...
Page 93: ...89...
Page 125: ...121 No 3 Axis 1 pause No 3 Axis 1 pause lamp No 3 Axis 1 STP...
Page 130: ...126...
Page 131: ......