4.3.16 Group C Screen 1
‘Group C Screen 1’ screen panel comes out when ‘C code’ button is touched in function selecting
menu. 8 digital input channels, which have their own specific functions, (1~8 channel) are
monitored in this screen panel. When the terminal has ‘ON’ value, green light is appears in the
sqare box beside the item name. When the terminal has ‘OFF’ value, green light is turned off
(black).
Figure 23 Group C screen 1
(1)
Digital Input 1: Inverter gets ‘RUN CMD’ (RUN) command from this digital input terminal when
REMOTE mode is selected (Set 1 in the ‘Group A screen1’).
Close: [green light] RUN.
Open: [no light] STOP.
(2)
Digital Input 2: Inverter gets ‘EMG SW’ (Emergency stop) command from this digital input
terminal.
Close: [green light] Emergency stop.
Open: [no light] no function.
(3)
Digital Input 3: Inverter gets ‘FLT RST’ (Flow Lookup Table Restore) command from this digital
input terminal. (Same function as ‘breakdown cancellation’ button on the operation controlling
screen panel (refer 4.3.5))
Close: [green light] Restore the system to normal state from the breakdown state.
Open: [no light] no function.
(4)
Digital Input 4: Inverter gets ‘VFD MODE’ command from this digital input terminal. Inverter is
operated in inverter running mode when accepting signal from digital input 4.
[referece 8]
Close: [green light] Inverter running mode.