61
Chapter
Chapter
Chapter
Chapter4
4
4
4.
.
.
. Inverter Operation
Inverter Operation
Inverter Operation
Inverter Operation
N5000 INSTRUCTION MAN
N5000 INSTRUCTION MAN
N5000 INSTRUCTION MAN
N5000 INSTRUCTION MANUAL
UAL
UAL
UAL
[Reference]
)
3
(
)
1
(
max
120
max
Screen
A
Group
motor
the
of
poles
of
number
the
Screen
A
Group
frequency
speed
×
=
4: [Displays ‘Out I’] generates voltage (0~10V) to show the inverter output current.
0V: Inverter output current is 0[A].
10V: Inverter output current is the rated current of the motor (Group H Screen 2).
(In case of ‘DAx gain’ value of the channel is ‘1’).
5: [Displays ‘Out V’] generates voltage (0~10V) to show the inverter output voltage.
0V: Inverter output voltage is 0[V].
10V: Inverter output voltage is input line voltage (Group A Screen 1). (In case of
‘DAx gain’ value of the channel is ‘1’).
6: [Displays ‘Out kW’] generates voltage (0~10V) to show the inverter output power.
0V: Inverter output power is 0[kW].
10V: Inverter output power is the same as the inverter capacity (Group A Screen
1). (In case of ‘DAx gain’ value of the channel is ‘1’).
(2)
DA 1~4 gain: set the analog output scale.
[Reference 9]
.
[Reference 9]
Example:
DA1=1
DA1 gain=1.2
Maximum frequency=60Hz
Analog output
0V: commanding frequency is 0Hz.
10V: commanding frequency is 72[Hz] ( 60(maximum)×1.2(DA1 gain)).