4.3.18 Group C Screen 3
‘Group C Screen 3’ screen panel comes out when DOWN (
) button in ‘Group C Screen 2’ screen
panel or UP (
) button in ‘Group C Screen 4’ screen panel is touched. Functions of all the 8
digital output terminals (1~8) are defined in this screen panel.
Figure 25 Group C screen 3
When touching any button in the sreen panel, 10KEY screen comes out for inputting values. (refer
to [Input way of 10KEY screen]).
(1) Digital output 1~8: These terminals can be customized for the various purposed. The functions
that are allocated to the numbers are as follows.
0: [Displays ‘No Used’] No function. Terminal is not used.
1: [Displays ‘Ready’] Close the terminal when the operation is ready to run in REMOTE
mode. (Refer to ‘controller selection’ in ‘group A Screen1’ screen panel.)
Close: ready to operate.
Open: not ready to operate.
[Caution]
Terminal is always open in LOCAL mode even when the operation is ready.
2: [Displays ‘Run’] Monitors RUN/STOP of the inverter.
Close: inverter is operating.
Open: inverter is stopped.
3: [Displays ‘Fault’] shows inverter fault regardless of its fault type.
Close: inverter fault (breakdown) has occured.
Open: inverter fault has not occurred.
4: [Displays ‘Alarm’] shows inverter alarm regardless of its alarm type.
Close: inverter alarm has occurred.
Open: inverter alarm has not occurred.
5: [Displays ‘Emg. SW’] shows ON/OFF state of the emergency stop switch.