9
C
C
C
Chapter3. Specification and Operation
hapter3. Specification and Operation
hapter3. Specification and Operation
hapter3. Specification and Operation
N5000 INSTRUCTION MANUAL
N5000 INSTRUCTION MANUAL
N5000 INSTRUCTION MANUAL
N5000 INSTRUCTION MANUAL
3.1 Specification
Item
Item
Item
Item
Specification
Specification
Specification
Specification
Inverter Type
Voltage type (Series connection with H-bridge circuit, multilevel
output)
Input Voltage
3 kV class: 1) 3300V ±10%, 2) 3000V ±10%
6 kV class: 1) 6600V ±10%, 2) 6000V ±10%
Input Transformer
Dry type multiphase coil transformer with built-in panel
Input Frequency
50Hz/60Hz
Input Rectification
3kV class: 18pulse diode rectification, 6k class: 36pulse diode
rectification
Input Current Harmonics
THD < 5%
Input Power-Factor
0.95 (20%~100% load condition)
Output voltage
3phase 0~3000V, 0~3300V, 0~6000V, 0~6600V
Output voltage level
3kV: 13 level (space voltage), 6kV: 25 level (space voltage)
Output Frequency
~120Hz
Rated operation range
100% load: continuous operation, 120% overload: 1min
Main power element &
modulation method
IGBT, PWM
Efficiency
96% (rated operation)
Cooling
Compulsive air cooling
Standard
IEC
Ambient temperature
0
℃∼
40
℃
Humidity
5%
∼
90% Non-condensing