44 Hydro-Control VI Operators Guide HD0456 Rev 1.7.1
2.8
The CALC Mode calibration procedure
Task
Action
Identify a good batch to use as a basis for the calibration.
Select a mix that has the following:
•
Correct final moisture
•
Stable dry and wet
readings (low deviation
values)
•
More than 5 unscaled
between dry and wet
average readings
Press the Menu button.
Press
Press the Mix Log button.
Press
Select the mix in the Mix Log that corresponds to the
selected good batch. Check the stability of the mix by
setting the mix log to Display Unscaled and looking at the
Dry and Wet Mix Deviation. These should be less than 3
and preferably less than 0.5. For sensors with multiple
measurement modes check the deviation for each available
mode.
Select the mix in the Mix Log
Press View Mix Trace.
Press
Press the Calibrate button.
Press
Choose which calibration mode is most appropriate for the
mix and press OK
Summary of Contents for Hydro-Control VI
Page 4: ...4 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 6: ...6 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 8: ...8 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 10: ...10 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 18: ...Navigation Chapter 2 18 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 20: ...Plant Operator Controls Chapter 3 20 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 34: ...Editing Recipes Chapter 6 34 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 40: ...Running the First Mix Chapter 7 40 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 56: ...Using Moisture Control Chapter 8 56 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 70: ...Setting Up User Accounts Chapter 11 70 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 72: ...Remote Support Chapter 12 72 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...
Page 86: ...Document Cross Reference Appendix C 86 Hydro Control VI Operators Guide HD0456 Rev 1 7 1 ...