2012 by Huchez Treuils S.A.S.
Translation of the original instructions manual
33
EN
Reproduction prohibited
With variable frequency drive
Use of the integrated keyboard
Adjusting limitation (current) using the frequency drive:
1/ Winch switched on displays
0000
, press save button
2/ Press browse button
several times until
C001
is displayed
3/ Press up button
until
C041
is displayed
4/ Press save button
5/ A value in amperes is displayed: increase to the maximum using the up button
, then press save
6/ Press the browse button
until
D001
is displayed
7/ Press the up button
until
D002
is displayed (current reading in ampere)
8/ Press save button
0000
is displayed (Load winch at the required stop value)
9/ Activate lifting (direct ampere reading). For example, 5 A at XX kg stop required.
10/ Return to
C041
using the save button
then browse
, save
and press up
. Adjust to
5A (for example) using the up
or down
button and save
.
11/ Press browse
D001
then save
and use.