AMP(H)41_MANUAL-en_R11 - 2019-03-28
Absolute Encoder AMP(H) 41
6.5
Bus status display
WARNING! NOTICE!
Destruction, damage and malfunction of the measuring system in case of
infiltration of foreign substances and damp!
The access to the LEDs has to be locked after the settings with the screw plug.
Tighten firmly!
The measuring system has two LEDs in the connection cover. A red LED (bus fail) to display
faults and a green LED (bus run) to display status information.
When the measuring system starts up, both LEDs flash briefly. The display then depends on
the operating status of the measuring system.
LED, green
Bus Run
ON
Ready for operation
OFF
Supply absent, hardware error
1 Hz
Incorrect parameterization of F_Parameters
3x with 5 Hz
PROFIsafe communication running, master requesting Operator
Acknowledgment
LED, red
Bus Fail
ON
No error, bus in cycle
1 Hz
Measuring system not addressed by the master,
no cyclical data exchange
OFF
Internal error, Bit 1 set in PROFIsafe status byte
For appropriate measures in case of error,
see chapter 11 “Troubleshooting and Diagnosis Options” on page 82.