Conductor insulation: PVC insulation
–
The 90°C flexible cables with copper conductors are used.
–
It is recommended that AC power cables be no longer than 30 meters
and DC power cables be no longer than 50 meters.
Table 6-4 Power terminal connection requirements
Port
Connection Method
Bolt
Specifications
Bolt Length
Torque
Mains input
Crimped DT terminal M16
55 mm
120 N·m
Bypass input
Crimped DT terminal M16
55 mm
120 N·m
Battery input
Crimped DT terminal M16
55 mm
120 N·m
Output
Crimped DT terminal M16
55 mm
120 N·m
PE
Crimped DT terminal M12
30 mm
47 N·m
Equipotential
ground point
Crimped DT terminal M6
12 mm
4.5 N·m
Table 6-5 Recommended input/output circuit breakers
Compone
nt Name
Specificat
ions
a
(200
kVA)
Specificat
ions
a
(300
kVA)
Specificat
ions
a
(400
kVA)
Specificat
ions
a
(500
kVA)
Specificat
ions
a
(600
kVA)
Specificat
ions
a
(700
kVA)
Specificat
ions
a
(800
kVA)
Mains
input
circuit
breaker
400 A/3P
630 A/3P
800 A/3P
1000
A/3P
1250
A/3P
1600
A/3P
1600
A/3P
Bypass
input
circuit
breaker
400 A/3P
630 A/3P
800 A/3P
1000
A/3P
1250
A/3P
1600
A/3P
1600
A/3P
Downstre
am
output
circuit
breaker
400 A/3P
630 A/3P
800 A/3P
1000
A/3P
1250
A/3P
1600
A/3P
1600
A/3P
a: recommended model when the short-circuit current where the circuit breaker is located is less
than 65 kA
UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
6 Installation
Issue 02 (2021-04-22)
Copyright © Huawei Technologies Co., Ltd.
66