Figure 4-4 Signal panel of the control module
(1) Ground terminal
(2) Parallel port 1
(3) BSC port 1
(4) Ready switch on
ECM 1
(5) ECM 1 indicators
(6) Parallel port 2
(7) BSC port 2
(8) Ready switch on
ECM 2
(9) ECM 2 indicators
(10) Dry contact card (11) Dry contacts
(12) Monitoring
display unit (MDU)
port
(13) RS485 port
(14) FE port
(15) COM2 port
(16) COM1 port
(17) Battery
temperature sensor
port
(18) Optional card
subrack cover
NO TE
Ports are protected by a security mechanism.
4.3.2 ECM
●
As a control interface for the entire system, the ECM communicates with each
module and provides a bus for communication between the dry contact card
and the system control card. The ECM ensures equalized output currents
between modules so that load power is equally shared.
●
The ECM provides module working status information to the monitoring
system.
●
The ECM controls the running of a single UPS and a parallel system, and
reports the UPS status information to other monitoring modules.
●
The system provides three types of CAN communication: monitoring CAN
communication, intra-rack parallel CAN communication, and inter-rack
parallel CAN communication.
●
The control module consists of one active ECM and one standby ECM.
●
Hot-swappable, 1 U high.