11
Technical Specifications
Table 11-1 Physical specifications
Item
400
kVA
500
kVA
600 kVA 800 kVA
Cabling mode
Routed in and out from the top
Cables can be routed in and out from the bottom if a
bottom cabling cabinet is configured.
IP rating
IP20
Communication
Supports dry contacts, RS485 ports, and FE ports. Supports
SNMP and Modbus.
Dimensions (H x
W x D)
● 2000 mm x 800 mm x
1000 mm (without
optional components)
● 2200 mm x 1200 mm x
1000 mm (with a bottom
cabling cabinet)
● 2000 mm x 1600 mm x
1000 mm (without
optional components)
● 2200 mm x 2400 mm x
1000 mm (with a
bottom cabling cabinet)
Weight
● UPS: < 800 kg
● UPS + bottom cabling
cabinet: < 910 kg
● UPS: <1300 kg
● UPS + bottom cabling
cabinet: < 1520 kg
Table 11-2 Environmental specifications
Item
Specifications
Operating
temperature
0–55°C
Temperature derating coefficient: not derated at 0°C–
40°C, derated to 0.9 at 41°C–45°C, derated to 0.8 at
46°C–50°C, and derated to 0.7 at 51°C–55°C
Storage temperature
–40°C to +70°C
UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
11 Technical Specifications
Issue 02 (2021-04-22)
Copyright © Huawei Technologies Co., Ltd.
153