Port
Silk
Screen
Description
COM
overload, Battery temp. abnormal, and
Battery EOD.
● Configure power segment settings based on
backup time.
DB26
MDU
Supports FE, RS485, I2C, CAN, and other signals.
Battery
temperature
sensor port
B_TEMP
Connects to an indoor battery temperature
sensor.
Southbound
communicatio
ns port 1
COM1
● Supported protocol: Modbus-RTU
● Connects to an ambient temperature and
humidity sensor over two wires.
Southbound
communicatio
ns port 2
COM2
● Supported protocol: Modbus-RTU
● Connects to a southbound device.
Network port
FE
● Supported protocols: Modbus-TCP, HTTPS, and
SNMP
● Connects to the network port on a PC.
● Network port for connecting to the web
service and for SNMP networking
Northbound
communicatio
ns port
RS485
● Supported protocol: Modbus-RTU
● Connects to a northbound network
management device or third-party network
management device over two wires.
NO TE
● Signal cables must be double-insulated twisted cables. If the cable length is within 25–
50 m, the cross-sectional area must be 0.5–1.5 mm
2
.
● RS485 cables and FE cables must be shielded cables.
are recommended wiring methods for DO ports.