Figure 6-52 Installing cables
Step 4 Connect signal cables. Bind cables to the cabinet nearby.
●
If you need to log in to the WebUI of the UPS monitoring system, connect the
network port on a PC to the FE port on the monitoring interface card.
●
If the UPS needs to connect to an external network management device,
connect the external network management device to the RS485 port on the
monitoring interface card.
NO TICE
– Do not bind signal cables and power cables together.
– RS485 cables and FE cables must be shielded cables.
UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
6 Installation
Issue 02 (2021-04-22)