4 Electrical Connections
Issue 12 (2019-01-15)
Copyright © Huawei Technologies Co., Ltd.
44
Figure 4-24
Stripping a cable (unit: mm)
Step 3
Insert the bare core wires into the surge port of the RS485 signal SPD, as shown by (1) in
Figure 4-25
Connecting cables to the surge port of the RS485 signal SPD
Verify that the RS485+ port on the analog-to-digital converter connects to surge port 1 or 7 on
the RS485 signal SPD, and that the RS485– port on the analog-to-digital converter connects
to surge port 5 or 11 on the RS485 signal SPD.
Step 4
Use a flat-head screwdriver to tighten the screws on the surge ports, as shown by (2) in
Step 5
Set
Baud rate
for the analog-to-digital converter to the same value as that for the
SmartLogger.
SmartLogger communications parameters can be set on the LCD or WebUI. For details,
see
6.2.26 Setting Communications Parameters
7.10.2.2 Setting RS485 Parameters
For details about the communications parameter configurations for the analog-to-digital
converter, see the delivered document.
Step 6
Connect each sensor to the analog-to-digital converter. For detailed operations, see the
documents delivered with the analog-to-digital converter or sensors.
After connecting the cables, log in to the embedded WebUI and set relevant parameters. For details,
see
7.8.4.2 Setting EMI Parameters
. The selected EMI model is
Sensor(ADAM)
.
The EMI cannot be detected automatically. You need to add this device manually on the LCD or
WebUI. For details about this operation, see