Parameter
Description
Recommended Value
Soft start time
Specifies the duration for the
power to gradually increase when
the inverter starts.
20
Soft start time after
grid failure
Specifies the time for the power to
gradually increase when the
inverter restarts after the power
grid recovers.
20
2.
Log in as
Special User
, choose
Monitoring
>
SUN2000
>
Running Param.
>
Adjustment
, and set the following parameters.
Parameter
Description
Recommended Value
Plant active power
gradient
Adjusts the rate of active power
rise due to light changes.
0
Active power change
gradient
Adjusts the change speed of the
inverter active power.
125%/s
If the maximum value is
50%/s, set this parameter to
50%/s
.
3.
Log in as
Special User
and choose
Settings
>
Active power control
. Ensure that
Active
power control
is set to
Disable
.
4.
Log in as
Special User
and choose
Settings
>
Export Limitation
.
Figure 7-68
Setting export limitation parameters