NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
153
Alarm
ID
Alarm
Alarm
Severity
Impact
Possible Cause
Solution
experiences overvoltage.
5.
The water pump races
due to a liquid level
detection fault.
6.
The humidifier pump is
blocked.
7.
The humidifier pump
races or is blocked due to
air pressure.
8.
The drainage capability
of the water pump
deteriorates, or the
drainpipe is blocked.
humidifier pump voltage.
5.
Rectify the liquid level
detection fault.
6.
Replace the pump if it is
faulty.
7.
Verify that the humidifier
water supply is normal,
and start the humidifier
pump multiple times.
8.
Replace the water pump
or dredge the drainpipe.
a180
Wet film
replaceme
nt due
Warning
The alarm
is
generated.
The humidifier pump has
exceeded the maximum
operating time.
Maintain or replace the
humidifier pump and clear
the accumulated runtime.
a181
Humidifie
r Pump
Timeout
Alarm
Warning
The alarm
is
generated.
The humidifier pump has
exceeded the maximum
operating time.
Maintain or replace the
humidifier pump and clear
the accumulated runtime.
a182
Water
Supply
Alarm
Major
The alarm
is
generated,
and the
humidifier
shuts
down.
1.
The water supply is
insufficient.
2.
The humidifier float has
dropped and is jammed.
3.
The humidifier float
interconnection terminals
are abnormal.
4.
The water inlet solenoid
valve cannot open.
5.
Cables of the water inlet
solenoid valve are not
properly connected.
1.
Verify that water supply
to the humidifier is
normal.
2.
Verify that the humidifier
float can float and drop
properly.
3.
Verify that the humidifier
float interconnection
terminals are properly
connected.
4.
Verify that water flows
into the humidifier pan
from the water inlet pipe
of the humidifier.
5.
Verify that cables of the
water inlet solenoid valve
are properly connected.
a184
Compress
or
preheating
alarm
Warning
The alarm
is
generated.
The compressor is
preheating.
Power on the device after the
compressor is preheated.
a190
Outdoor
fan driver
fault lock
Critical
The alarm
is
generated,
and the
compresso
r shuts
1.
The cables to the outdoor
fan are loose or
damaged.
2.
The outdoor fan is faulty.
3.
The outdoor unit main
control board is faulty.
1.
Check the cables to the
outdoor fan.
2.
Maintain or replace the
outdoor fan.
3.
Maintain or replace the
outdoor unit main control