Figure 3-44
Securing a differential pressure sensor
Step 2
Connect a pressure inlet tube to the + mark on the micro differential pressure sensor and route
it to the cold aisle through the hole on the top of the cabinet. Connect another pressure inlet
tube to the – mark on the micro differential pressure sensor and route it to the hot aisle
through the hole on the top of the cabinet, as shown in step 2 in
Step 3
Connect the three terminals of 12 V DC, GND, and 0-5 V feedback of differential pressure
sensor cable to ports 1, 2, and 3 (from left to right) on the X303 terminal, as shown in
Figure 3-45
Connecting a differential pressure sensor