NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
156
Symptom
Possible Cause
Solution
generates
excessive
noises.
normal range.
Refrigerant oil is insufficient.
Add refrigerant oil.
The transport sheet metal is not
removed from a compressor.
Remove the sheet metal.
An indoor
fan fails to
start.
The switch of the indoor fan is not
turned on.
Check the switch of the indoor fan.
An indoor fan is damaged.
Replace the indoor fan.
The interconnection terminals for
the fans are not securely
connected.
Secure the interconnection terminals
again.
The heating
function is
unavailable.
The electric heater temperature
switch is being protected.
Check the temperature switch and
replace it if it is faulty.
The electric heater is not switched
on.
Check the electric heater switch.
An electric heater is burnt out.
Disconnect the power supply and
check whether the electric heater is
damaged by checking the electric
heater resistance properties with an
ohmmeter.
No water is
supplied to
the water
inlet
solenoid
valve of the
humidifier.
The upstream water supply is
faulty or the water pressure is
below the lower threshold.
Restore the water supply.
The water inlet solenoid valve is
blocked or faulty.
Replace the water inlet solenoid
valve.
The cable to the water inlet
solenoid valve is incorrectly
connected.
Reconnect the cable.
The humidifier float jams and fails
to fall down, or the cable
connection is faulty.
Manually operate the float or
reconnect the cable.
The
humidifier
pump fails
to supply
water.
The humidifier pump is faulty or
the cable connection is incorrect.
Replace the humidifier pump or
reconnect the cable.
The humidifier pump is blocked.
Replace the humidifier pump.
The humidifier pump is blocked
due to atmospheric pressure.
Restart the humidifier pump.
The water
overflows
the
NetCol5000-
A.
The drainpipe does not connect to
the pump, or the lift between the
drainpipe and the water chiller is
set to an appropriate value.
Ensure that the drainpipe is properly
connected to the pump and that the
lift of the drainpipe is lower than 4
meters.
The condensate pump is faulty.
Replace the condensate pump.