5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
200
The new module must be installed in the same slot as the faulty module. Otherwise, the air
conditioner may fail to work properly.
Before replacing a main control module, disconnect the network cables from the main
control module.
The module can be maintained only from the rear door.
Figure 5-50
Module
(1) Main control module
(2) Auxiliary power supply module
(3) PSU 1
(4) PSU 2
Procedure
Step 1
On the controller home screen, tap
Shutdown
, and turn off the air conditioner switch in the
PDC.
Exercise caution because the device is still energized after it is shut down on the controller
home screen.
Step 2
Open the rear door and remove the air filter.
Step 3
Flip the clip on the module downwards, as shown by (1) in