NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
26
3.2.2 Material Preparations
Materials to be prepared onsite are classified into three categories:
Mandatory: mandatory configuration. This material is provided by Huawei and can be
found in delivered fittings.
Optional: This material can be purchased from Huawei or prepared by customers.
Engineering purchase: This material will not be delivered by Huawei, and customers
need to purchase it.
3.2.2.1 (Optional) Refrigerant R410A
Do not use low-quality refrigerant. Huawei is not responsible for any damage caused by
low-quality refrigerant.
Follow these suggestions to choose high-quality refrigerant:
1.
Use high-quality brands such as DuPont, Daikin, or Honeywell.
2.
Contact the refrigerant producer to confirm the refrigerant authenticity.
3.
Check the refrigerant by following the steps shown in
: Keep the refrigerant
indoors at a constant temperature and humidity for 24 hours. Use a thermometer to
measure the external surface temperature of the refrigerant container, and connect a
pressure gauge to the container to measure its internal pressure. Determine the saturation
pressure that corresponds to the measured external surface temperature according to
and calculate the deviation from the measured internal pressure. If the
deviation is more than 0.2 MPa, the refrigerant is not qualified and should be replaced.
Figure 3-2
Checking refrigerant
Table 3-7
Mapping between temperatures and R410A saturation pressure
Temperature
(°C)
Saturation
Pressure-S
urface
Pressure
(MPa)
Temperature
(°C)
Saturation
Pressure-S
urface
Pressure
(MPa)
Temperat
ure (°C)
Saturation
Pressure-S
urface
Pressure
(MPa)