4.7 Charging the Remaining Refrigerant
Prerequisites
Check that the outdoor unit switch is turned on before you start the compressor.
Remove the refrigerant steel vessel after checking that no more refrigerant is required.
Charge refrigerant in an amount exactly as required by
4.1.1 Refrigerant Charge Amount
Otherwise, the devices may be damaged.
Procedure
Step 1
Charge refrigerant on the basis of the precharging.
If there are no low-temperature components, open the low-pressure valve of the pressure
gauge, and charge the remaining refrigerant from the low-pressure needle valve in small
flow or intermittently, as shown in
If there are low-temperature components, open the low-pressure valves of pressure gauge
1 and pressure gauge 2, and charge the remaining refrigerant from the low-pressure
needle valves in small flow or intermittently, as shown in
Step 2
On the home screen, choose
Running
>
Device Details
>
Compressor
, and view
Suction
pressure
and
Discharge pressure
to determine whether they are within normal ranges. The
normal suction pressure range is 0.7–1.2 MPa.
lists the proper discharge pressure
range. Choose
Running
>
Device Details
>
EEV
, and view the
EEV suction overheating
degree
. The normal overheating degree should be in the range of 8–15°C.
Table 4-12
Normal discharge pressure ranges
Ambient Temperature
Discharge Pressure Range
< 15°C
1.5–2.5 MPa
15–35°C
1.5–3.1 MPa
35–45°C
2.5–3.8 MPa
> 45°C
3.1–4.15 MPa
Step 3
After charging refrigerant, close all valves.
----End
4.8 Startup wizard
Prerequisites
Check that refrigerant is fully charged before performing the wizard startup.