4 Commissioning
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
112
Step 4
On the home screen of any teamwork controlled air conditioner, tap
. If the teamwork
control succeeds, the teamwork topology of the air conditioner in the group is displayed, as
shown in
describes the note for the screen.
Figure 4-25
Teamwork topology
Table 4-11
Notes for the screen
No. Parameters Note
1
ON/OFF/NA
On
indicates that the precision air conditioner is started and
Off
indicates that the precision air conditioner is shut down.
NA
indicates that the precision air conditioner is offline.
2
01, 02, 03
Indicates the device address. 01 is the master one and the rest are all
slave ones.
NOTE
If the master one offline, the teamwork networking failed.
3
Active/Stand
by
Active: properly responds to the requirement control.
Standby: responds to the requirement control when
Active
is faulty
(critical alarms, shutdown, and offline) or
Active
cannot meet
cooling requirements.
4
M/S
M indicates the master unit, and S indicates a slave unit. Blue
indicates that the device is operating, and gray indicates that the
device is idle.
5
Frame:
green/non-gr
een
A device with green frame indicates the device itself,
as shown in
.
A non-green frame indicates the other device in the group,
as shown in
.
6
Ground
Red indicates that a critical alarm is generated,