NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
4 Commissioning
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
85
If the precision of the pressure gauge is too low to display 60 Pa (absolute pressure), ensure that the
pressure gauge pointer stays at the minimum scale while vacuumizing the cooling system. Preserve the
pressure for 1 hour, and make sure the displayed pressure does not increase obviously.
----End
4.1.3 Precharging Refrigerant
Prerequisites
Before charging refrigerant, ensure that air is exhausted from the gas pipe connecting to the
refrigerant cylinder.
Context
Wear antifreeze gloves when performing refrigerant-related operations.
Charge refrigerant (R410A) right after checking that the cooling system does not leak and
the vacuum level meets the requirements.
Procedure
Step 1
Remove the vacuum pump from the vacuumizing equipment, and replace the vacuum pump
with a refrigerant cylinder, as shown in