3.11.2.1 Connecting the Outdoor Unit On/Off Signal Cable
Context
The outdoor unit signal cable can connect to a dry contact or an RS485 port (by default).
Outdoor fan control mode
is set to
Communicate
by default. If the signal cable connects to
a dry contact, set
Settings
>
System Settings
>
Outdoor Fan
>
Outdoor fan control mode
to
Dry contact
.
If the signal cable connects to a dry contact while
Outdoor fan control mode
is set to
Communicate
, the
Outdoor fan communication failure
alarm will be displayed on the
LCD.
If the signal cable connects to an RS485 port while
Outdoor fan control mode
is set to
Dry contact
, the
Comp discharge HP
alarm will be displayed on the LCD after the
compressor starts.
If the
Outdoor fan control mode
is changed on the screen, the screen will restart.
Procedure
Step 1
Route the cable through the cable hole on the top or at the bottom of the cabinet.
Step 2
Connect the signal cable.
Remove the female connector from the interconnection terminal. After the cable is connected
to the female connector, reconnect the connector to the interconnection terminal.
(RS485 connection) Connect one end of the cable to points 1, 2, and 3 on the external
signal port X302 and the other end to ports 3, 4, and 5 on the outdoor unit.