5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
199
Figure 5-49
Installing a strong-current box
Step 7
Reconnect the cables and terminals shown in
Step 8
Install the air filter and close the rear door.
Step 9
Power on the device and tap
Startup
on the home screen. Ensure that the air conditioner is
running normally without any alarms.
----End
5.4.13 Replacing Main Control Module, Auxiliary Power Supply
Module, or PSU
Prerequisites
The main control module, auxiliary power supply module, or PSU needs to be replaced.
A spare main control module, auxiliary power supply module, or PSU of the same model
is available and functional.
Context