Type
Tool
Hydraulic pliers
Heat shrink tubing
Heat gun
Binding strap
Personal
protective
equipment
(PPE)
Safety gloves
Safety goggles
Anti-dust
respirator
Safety boots
4.3 Determining the Installation Position
4.3.1 Environment Requirements
Basic Requirements
●
Do not install the inverter in working or living areas.
●
If the device is installed in public places (such as parking lots, stations, and
factories) other than working and living areas, install a protective net outside
the device, set up a safety warning sign to isolate the device, and prevent
unauthorized personnel from approaching the inverter. This is to avoid
personal injury or property loss caused by accidental contact or other reasons
during device operation.
●
Do not install the inverter in areas with flammable materials.
●
Do not install the inverter in areas with explosive materials.
●
Do not install the inverter in areas with corrosive materials.
●
Do not install the inverter where its enclosure and heat sinks are easily
accessible, because the voltage is high and these parts are hot during
operation.
●
Install the inverter in a well-ventilated environment for heat dissipation
●
If the inverter is installed in an airtight environment, a heat dissipation device
or ventilation device must be installed to ensure that the indoor ambient
temperature is not higher than the external ambient temperature during
operation.
●
You are advised to install the inverter in a sheltered place or install an awning
over it.
●
The inverter will be corroded in salt areas. Before installing the inverter
outdoors in salt areas, consult Huawei. A salt area refers to the region within
SUN2000-(196KTL-H0, 200KTL-H2, 215KTL-H0)
Series
User Manual
4 Installation
Issue 07 (2021-07-08)
Copyright © Huawei Technologies Co., Ltd.
21