Figure 7-9 Feature parameters (advanced user)
----End
Parameters
No.
Parameter
Description
Remarks
1
MPPT multi-peak
scanning
When the inverter is used in
scenarios where PV strings are
greatly shaded, set this parameter
to Enable, and then the inverter
will perform MPPT scanning at
regular intervals to locate the
maximum power.
-
2
MPPT multi-peak
scan interval (min)
Specifies the MPPT scanning
interval.
This parameter is displayed
when MPPT multi-peak
scanning is set to Enable.
3
RCD enhancement
RCD refers to the residual current
of the inverter to the ground. To
ensure device and personal safety,
RCD should be limited to the
specified value in the standard. If
an AC switch with a residual
current detection function is
installed outside the inverter, this
function should be enabled to
reduce the residual current
generated when the inverter is
running, thereby preventing the
AC switch from misoperations.
-
SUN2000-(196KTL-H0, 200KTL-H2, 215KTL-H0)
Series
User Manual
7 Man-Machine Interactions
Issue 07 (2021-07-08)
Copyright © Huawei Technologies Co., Ltd.
62