Alarm
ID
Alarm Name
Alarm
Severity
Cause
Troubleshooting Suggestions
61440 Faulty
Monitoring
Unit
Minor
Cause ID=1
1. The flash memory is
insufficient.
2. The flash memory has
bad sectors.
Turn off the AC output switch
and DC input switch, and then
turn them on after 15 minutes.
If the fault persists, replace the
monitoring board or contact
your dealer or Huawei
technical support.
NO TE
If you cannot rectify faults with the measures listed in troubleshooting suggestions, contact
your dealer or Huawei technical support.
SUN2000-(196KTL-H0, 200KTL-H2, 215KTL-H0)
Series
User Manual