15. Enter
sr
to view the system revision information. A sample output for a BL890c i2 is shown
below. The BL890c i2 will show four blades composing the serve blade, a BL870c i2 will
show two. If the output does not show all of the blades expected, then there is a problem
which must be resolved before proceeding. Reseating the Blade Link or individual blades may
correct server blade conjoining problems.
[ilo002264fed1da] CM:hpiLO-> sr
SYSREV
Revisions Active Pending Bay 5 Bay 6 Bay 7 Bay 8
----------------------------------------------------------------------------
iLO FW : 01.30.30 01.30.30 01.30.30 01.30.30 01.30.30
System FW : 01.24 01.24 01.24 01.24 01.24
MHW FPGA : 01.14 01.14 01.14 01.14 01.14
Power Mon FW : 03.04 03.04 03.04 03.04 03.04
Front Panel HW : 03.00 03.00 03.00 03.00 03.00
PRS HW : 02.07 02.07 02.07 02.07 02.07
IOH HW : 02.02 02.02 02.02 02.02 02.02
16. If the
sr
output indicates that the firmware is not consistent across all of the blades, which
should only be due to a new Upgrade Blade with different firmware version being added,
then complete a second server firmware update. Update the system to the same firmware
version used previously for the existing servers. An example of
sr
output indicating a firmware
inconsistency is shown below.
[ilo002264fee2de] CM:hpiLO-> sr
SYSREV
Revisions Active Pending Bay 5 Bay 6 Bay 7 Bay 8
----------------------------------------------------------------------------
iLO FW : --.--! 01.30.29 01.30.29 01.01.02 01.01.02
System FW : --.--! 01.24 01.24 01.08 01.08
MHW FPGA : --.--! 01.14 01.14 01.12 01.12
Power Mon FW : 03.04 03.04 03.04 03.04 03.04
Front Panel HW : 03.00 03.00 03.00 03.00 03.00
PRS HW : 02.07 02.07 02.07 02.07 02.07
IOH HW : 02.02 02.02 02.02 02.02 02.02
Note(s):
! = FW mismatch, update needed
If an update is required, it may need to be completed using the HPSUM Force Install option
for both the iLO 3 and system firmware bundles. When finished, log back into the iLO 3 MP
of the Monarch blade and enter
sr
from the Command Menu to verify that the firmware levels
on all conjoined blades are now consistent and up to date.
17. Exchange the System Information Parameters by following the steps below. For more information
regarding the information contained in the System Information Parameters, see
“Blade link
and system information parameters” (page 80)
.