Table 12 Server blade environmental specifications
Non-Operating Range
Maximum Rate of Change
Recommended
Operating Range
Operating Range
Parameter
-40°C to 60°C (-40°F
to 140°F)
10°C (50°F) / hr with
tape
20°C (68°F) / hr without
tape
20°C to 25°C (68°F
to 77°F) (up to 5000
feet)
5°C to 35°C (41°F to
95°F) (up to 5000 feet)
Temperature
90% at 65°C (149°F)
noncondensing
30% per hour
noncondensing
40-60% at 35 degrees
35°C (95°F)
noncondensing
15-80% at 35°C (95°F)
noncondensing
Relative Humidity
Troubleshooting the environment 107