4 213 321 V01 KDT RegelModul Solar EN.docx
38 / 95
Parameters
Designation
Value Min.
Max.
Comments
R
W
08-070
High solar yield
switch-on
threshold
50%
0
100
If a comparison of the current solar output and the
reference output produces a factor above the setting
value and if the reduced storage tank reference value
(08-062 - 08-072) is exceeded, recharging with a
conventional heat generator is blocked and only
permitted at a reduced reference value. If the factor is
10% (fixed hysteresis) below the setting value,
the normal storage tank reference value (08-062) is
reactivated except if the long-term block prevents it
(08-071).
If the reduced reference value is undershot, the
normal storage tank reference value (08-062) is
immediately reactivated. The calculated solar
nominal output is directly related and is taken into
account in this.
4 4
08-071
High daily yield
switch-on
threshold
100%
0
100
If the daily yield is above the setting value and if the
normal storage tank reference value (08-062) is
exceeded, recharging with a conventional heat
generator is only permitted at a reduced reference
value for 18 h (long-term block). After 18 h the
normal storage tank reference value (08-062) is
reactivated, except if there is still a high solar output
(see 08-070). If the reduced reference value is
undershot, the normal storage tank reference value
(08-062) is immediately reactivated. The calculated
solar nominal output is directly related and is taken
into account in this.
4 4
08-075
Recharging
switch-on
difference PBL
8 K
5.0
50.0
If the temperature at the storage tank sensor is less
than the active storage tank reference value - switch-
on the hysteresis (08-063) and if the temperature
difference in relation to the recharging sensor rises
above the setting value, recharging is enabled.
4 4
08-076
Recharging
switch-off
difference PBL
4 K
2.0
20.0
If the temperature at the storage tank sensor is
greater than the active storage tank reference value
or if the temperature difference in relation to the
recharging sensor drops below the setting value,
recharging is blocked.
4 4
08-077
Discharge
switch-on
difference PEL
10 K
5.0
50.0
If the temperature at the storage tank sensor is
greater than the active storage tank reference value
+ 2 K and if the temperature difference in relation to
the discharging sensor rises above the setting value,
discharging is enabled.
4 4
08-078
Discharge
switch-off
difference PEL
5 K
2.0
20.0
If the temperature at the storage tank sensor is less
than the active storage tank reference value or if the
temperature difference in relation to the discharging
sensor drops below the setting value, discharging is
blocked.
4 4
08-041
Alloc. to
storage tank
number
0
0
32
Allocation to storage tank number (for communication
solar telegrams)
0: Not allocated
1: Heating buffer (DIP 0)
4 4
30-012
Alloc. inp.
THT - high-
temperature
disch.
0=OFF
Data point deleted
4 4