4 213 321 V01 KDT RegelModul Solar EN.docx
72 / 95
12.5.1. Menu: Collector - Parameters -
Collector protection, starting aid, …
Parameters
Designation
Value
Min.
Max.
Comments
R
W
08-005
Collector
protection
option
1
0
1
The setting sets the protection function for the
collector overheating:
0 = No collector protection
3 3
08-010
Collector
protection
temperature
120 °C
80.0 180.0
If the temperature at the collector sensor increases
above the setting value, solar charging is blocked.
4 4
08-011
Collector
maximum
temperature
100 °C
80.0 150.0
If the temperature at the collector sensor increases
above the setting value with active overheating
protection (08-005), solar charging is enabled.
4 4
08-012
Collector
minimum
temperature
20 °C
-15.0 90.0
Minimum collector temperature at which the solar
plant is enabled/blocked (hysteresis fixed at -5K)
4 4
08-013
Collector frost
protection
temperature
-20 °C
-50.0 10.0
Deactivated if setting value -50 °C.
Frost protection mode active if the average outside
temperature falls below the set value. Frost protection
mode is terminated if the setting value is exceeded by
2K (hysteresis fixed).
4 4
08-015
Collector
starting aid
0
0
1
"If the collector temperature can only be registered
with insufficient accuracy, optimisation is possible
using the starting aid function. Due to a positive
temperature change at the collector sensor, the solar
pump is switched on for a limited run time (08-017).
The pump switches off again at the end of the time.
TKO is measured. If the temperature difference in
relation to the storage tank is sufficient, the solar
pump switches "On". If the switch-on criteria are not
met, the solar pump is switched on again after
a variable waiting time (15 to 100 minutes).
The waiting time is defined on the basis of TKO and
the temperature change.
A starting aid for the solar pump is activated in
position "on"."
4 4
08-017
Pump running
time starting aid
2 min
,5
20.0
Run time of the pump with active collector starting
aid function.
4 4
08-020
P share calc.
(Xp) coll. ctrl.
pump ctrl
20 K
10
50
The collector controller has a PID control. The set P
share determines at which reference value deviation
100% setting command is generated for the speed
control.
5 5
08-021
Collector
controller reset
time (Tn)
10 min
0
30
The reset time influences the speed at which the
speed control corrects a reference/actual value
deviation. The setting value defines after how many
minutes a doubling of the gap from the minimum
manipulated variable (08-035) is required.
5 5