4 213 321 V01 KDT RegelModul Solar EN.docx
51 / 95
Parameters
Designation
Value
Min.
Max.
Comments
R
W
30-021
Alloc. TWZ - circ. hot water
temp. input
0=OFF
Allocation of input (VE1, VE2,
VE3/IMP, VE1/FE-1, etc.)
3 3
30-023
Alloc. inp. pulse circulation
function
0=OFF
Allocation of input (VE1, VE2,
VE3/IMP, VE1/FE-1, etc.)
3 3
32-032
Alloc. PWZ DHW pump
circulation output
0=OFF
Allocation of the output (VA1, VA2,
VA3, VA1/FE-1, etc.)
3 3
Parameters
Designation
Value
Min.
Max.
Comments
R
W
05-054
Ref. temp.
circulation
45 °C
0.0
90.0
Specification of a reference value for the circulation.
If the temperature at the circulation sensor TWZ
drops below the reference value minus hysteresis,
the circulation pump CIRCU is activated.
3 3
05-070
PWZ runtime
with pulse contact
control
3 min
2
30
If the circulation pump is operated with pulse control,
this value defines the run time of the pump PWZ.
3 3
05-071
PWZ off-period
with pulse contact
ctrl
10 min
0
240
After the run time of the pump PWZ has expired,
operation is blocked for this time.
3 3
11.18. Legionella protection (LEGIO option)
A legionella protection function can be programmed using the special time program on the control module.
If the legionella protection function is active, i.e. parameter (05-014) does not equal 0 and there is an enable from
the time program, the output is active for circulating the tank.
If the LegioSoll reference temperature set in the special time program is reached, the attempt is made to hold it for the
holding time set by parameter (05-043).
Legionella enable at 60 °C, 59 °C and lower = OFF
Standard day programs legionella
Legio 60 °C
00:00
- 16:00 /
10 °C
16:00
- 18:00 /
60 °C
18:00
- 24:00 /
10 °C
Legio 65 °C
00:00
- 16:00 /
10 °C
16:00
- 18:00 /
65 °C
18:00
- 24:00 /
10 °C
Legio 70 °C
00:00
- 16:00 /
10 °C
16:00
- 18:00 /
70 °C
18:00
- 24:00 /
10 °C
Legio 75 °C
00:00
- 16:00 /
10 °C
16:00
- 18:00 /
75 °C
18:00
- 24:00 /
10 °C
Legio OFF
00:00
- 24:00 /
10 °C