4 213 321 V01 KDT RegelModul Solar EN.docx
81 / 95
The overview below relates to the first storage tank (storage tank 1)
13.1.1. Menu: Solar storage tanks - Information
Parameters
Designation
Value
Min.
Max.
Comments
R
W
00-016
TU storage tank
bottom temp.
31.6 °C
0.0
100.0
Current temperature in the solar storage tank
bottom.
0 7
22-102
PPS discharge pump
tank output
0
0
1
Output PPS charging pump storage tank
4 7
01-016
Current setpoint tank
bottom temp.
55 °C
0.0
100.0
Calculated reference value for storage tank
temperature bottom
3 7
01-052
UVP switching valve
current state
0
0
1
UVP switching valve current state
3 7
00-015
TO storage tank top
temp.
--- °C
0.0
100.0
Current temperature in the buffer / storage
tank top. This value can be local or from the
system controller buffer (00-015) / DHW
storage tank (00-004).
0 7
01-015
Current setpoint tank
top temp.
55 °C
0.0
100.0
Calculated reference value for storage tank
temperature top
3 7
22-106
PTWTd speed WT
pump decentral
0%
0
100
PWT heat exchanger pump speed
decentralised
4 7
00-121
TWVz heat exchanger
decentral temp.
--- °C
0.0
150.0
Temperature heat exchanger TWVx -> option
heat exchanger decentralised
3 7
00-004
TB hot water
temperature
--- °C
0.0
100.0
Temperature additional hot water storage
tank TB -> option discharge PPS
2 7
00-003
THR heating circuit
return temperature
--- °C
0.0
100.0 Option return flow increase
2 7
22-107
Switching valve return
flow incr. output
0
0
1
Switching valve return flow incr. output
4 7
00-007
TFK solid-fuel boiler
temperature
--- °C
0.0
100.0 FK solid-fuel boiler option
0 7
22-108
PFK solid-fuel boiler
pump rot. speed
0%
0
100
PFK solid-fuel boiler pump rot. speed
4 7
22-113
PSL speed pump
storage tank loading
0%
0
100
Manipulated variable solar pump, with the
pump connected to a storage tank.
0 7
22-101
WWL hot water
charging pump output
0
0
1
WWL hot water charging pump output
3 7
22-109
Switching valve zone
charging output
0
0
1
UZO switching valve zone charging output
4 7
13.1.2. Menu: Solar storage tank - Function name
– Configuration
Parameters
Designation
Value
Min.
Max.
Comments
R
W
04-005
Function name
Solar storage tank 1
13
0
0 0
30-003
Alloc. TO1 - tank 1 top
temp. input
0=OFF
Allocation of input (VE1, VE2,
VE3/IMP, VE1/FE-1, etc.)
3 3
30-007
Alloc. TB hot water
temp. input
0=OFF
Allocation of input (VE1, VE2,
VE3/IMP, VE1/FE-1, etc.)
4 4
30-010
Alloc. TU1 - tank 1
bottom temp. input
2=VE2
Allocation of input (VE1, VE2,
VE3/IMP, VE1/FE-1, etc.)
3 3
32-024
Alloc. PWM output
PSL pump tank charg.
0=OFF
Allocation of the output
(VA10/PWM, VA10/PWM on
FE-1, etc.)
3 3