4 213 321 V01 KDT RegelModul Solar EN.docx
89 / 95
THR
Toxmax_RLA
RLA_combi on
TOx
TOxref
30
50
90
70
80
40
0
20
10
60
RLA on
RLAmax
(07-008)
RLAon > 10K
(08-080)
RLAoff 5K
(08-081)
13.1.11. Menu: Solar storage tank - RLA (return flow increase option)
Parameters
Designation
Value Min.
Max.
Comments
R
W
08-103
Option return
flow increase
0
0
1
Return flow increase option
Used for buffer discharging with the objective of
providing heat for the heating system. The heating
circuit return is preheated via the buffer as soon as
this is higher by a definable temperature difference
and supplied in the boiler return and possibly post-
heated using the heat source. CAUTION: storage
tank type (08-055) must be at 1 = heat storage tank!
TxO > THR + switch-on difference (08-080) & TxO <
maximum temperature return increase (07-008) =
UHR active (hysteresis 2K)
TxO < THR + switch-off difference (08-081) or TxO
> maximum temperature for the return increase
(07-008) = function blocked
4 4
30-009
Alloc. THR HC
return temp.
input
0=OFF
Allocation of input (VE1, VE2, VE3/IMP,
VE1/FE-1, etc.)
4 4
32-003
Alloc. sw valve
return flow incr.
output
0=OFF
Allocation of the output (VA1, VA2, VA3,
VA1/FE-1, etc.)
4 4