4 213 321 V01 KDT RegelModul Solar EN.docx
66 / 95
0
5
10
15
20
25
30
Charging blocked
Charging free
Charging
blocked
(08-012)
(08-012) -5K
Charging free
TKO
Tkmin off
Tkmin
12.3.2. Menu: Collector - Function name
– Configuration
Parameters
Designation
Value
Min.
Max.
Comments
R
W
04-005
Function name
Collector 1
13
0
0
0
32-011
Alloc. PWM output
PS pump solar
8=VA10V/PWM
Allocation output
0-10 V/PWM solar pump
0=OFF
8=VA10V/PWM
12=VA10V/PWM FE1
16=VA10V/PWM FE2
3
3
08-046
Delete partial yield
0=NO
Delete partial yield
Operating command
0 = No function
3 = Reset partial yield
0
0
12.4. Collector
– limit temperatures
12.4.1.
Collector minimum temperature (parameter 08-012)
If the collector temperature at sensor TKO is greater than the collector minimum temperature TKmin (08-012),
solar charging is enabled.
TKO > TKOmin (08-012) results in charging enable
TKO < TKOmin (08-012)
– 5K (fix) results in charging block