44
4 211 326 / 01
OvERvIEW Of SETTIngS
HEAT GENER.
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
H-GEN model
1/ 2/ 5
HF
2
Start-up protection H-GEN
OFF/ 3
HF
3
Minimum temperature limit H-GEN
5/ 48/ 65/ 75
°C
HF
4
Maximum temperature limit H-GEN
75/ 85 °C
HF
5
Mode of action minimum temperature limit H-GEN
1
HF
6
Sensor mode operation for H-GEN
1
OEM
7
Minimum burner running time
2 min
HF
8
Burner switching difference I
6 k
HF
9
Burner switching difference II
12 k
HF
10
Time-out stage II
10
HF
11
Release mode stage II
1
HF
12
DHW charging mode 1-2 stage
2
HF
13
Lead time, boiler circuit pump
1 min
HF
14
Follow-on time, boiler circuit pump or parallel boiler release
5 min
HF
15
Search time feed pump, primary pump
5 min
HF
16
Exhaust gas temperature monitoring
OFF
HF
17
Exhaust gas limit value
200 °C
HF
18
Boiler gradient
OFF
OEM
19
Modulation P-portion Xp
5 %/ k
OEM
20
Modulation scanning time Ta
20 s
OEM
21
Modulation adjustment time Tn
180 s/ °C
OEM
22
Modulation running time
12 s
HF
23
Modulation starting time
200 s
HF
24
Modulation start-up output
70
HF
25
Outside temperature block
OFF
OEM
26
Basic charge elevation
0 k/ 10k
OEM
27
Minimum temperature limit, heating circuits
5/ 38/ 65 °C
HF
28
Switching difference, minimum temperature limit Heating
circuits
2 k
OEM
29
H-GEN forced discharge
OFF
HF
30
OEM Maximum limit
110 °C
OEM
31
Minimum load control
OFF
OEM
34
Output limitation heating
100 %
HF
35
Output limitation hot water
100 %
HF
36
ET blocking 2.burner stage
OFF
HF
37
Running time meter
1
HF
38
DHW release regulator (CD)
ON
HF
39
Emergency operation temperature H-Gen (e.g. for 70-8)
70 °C
HF
40
Heat balance (from V3.2)
ON
HF
41
Reset heat balance
HF
42
Volumetric fl ow rate
0,0 l/ min
HF
0,0 l/ IMP
43
Density, medium
1,00 kg/ l
HF
44
Specifi c thermal capacity, medium
4,2
HF
RESET ST-1 Reset counters starts and running time, stage 1
OEM
RESET ST-2 Reset counters starts and running time, stage 2
OEM