![hopf 8029NTS-V2/GPS Technical Manual Download Page 28](http://html1.mh-extra.com/html/hopf/8029nts-v2-gps/8029nts-v2-gps_technical-manual_2161869028.webp)
C
OMMISSIONING
28 / 121
GPS - NTP Time Server with LAN Interface 8029NTS-V2/GPS - V08.00
hopf
Elektronik GmbH
Nottebohmstr. 41
• D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]
6
Commissioning
This chapter describes commissioning of the Time Server 8029NTS/GPS.
6.1
General Procedure
Overview of the general commissioning procedure:
•
Finish the installation process completely
•
Switch on the device
•
Wait until the booting phase is finsihed (Duration approx. 2 min.
– finished when the
green NTP LED is lit on)
•
Using the SEARCH Function of the
hmc
-
Network Configuration Assistant
in order
to access the Time Server 8029NTS/GPS and set the basis LAN parameters (e.g.
DHCP). Afterwards connect to the WebGUI of the Time Server 8029NTS/GPS via
Web browser
OR
connect directly with the factory default IP-address (192.168.0.1) to the WebGUI of
the Time Server 8029NTS/GPS via Web browser
•
Log in as
"master"
•
Change default passwords for
"master"
and
"device"
In the
DEVICE tab
•
Set all required LAN parameters (e.g. entry of DNS server) in
NETWORK tab
if
necessary
•
Check current settings in
NTP tab
and modify according to individual needs as
necessary
•
Parametrize following values of the Sync Source (here Module 8024GPS) in
GPS
SYNC SOURCE
tab:
o
Set current UTC time
o
Set the local difference time to UTC
o
Set or deactivate the changeover times for summer/winter time
o
Set local position (if not known as 0)
o
Check values for reception mode, SyncON/SyncOFF Timer and status OC
Trigger a
Module Reset
after the above mentioned entries
During first commissioning it is mandatory required to configure the
difference time to UTC and the changeover times for summer/winter time
respectively to deactivate them one time. Otherwise synchronization via
GPS will not be possible and a "Sync Source Error" is indicated.
•
Check for
Module Error
in register
GPS SYNC SOURCE
•
Parametrize optional functions e.g. SNMP or SINEC H1 time datagram
•
If all base settings are carried out correctly and there is GPS reception, the
GENERAL
tab
should look like this after approx. 30 min.: