C-1
A P P E N D I X C
Specifications
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
VISTA-128FBPN CONTROL
Physical:
18"H X 14-1/2"W X 4.3"D
Electrical:
Primary Power:
From ADEMCO No. 1451 Transformer with enclosure; rated 18VAC, 72VA.
Backup Battery:
12VDC, 12AH min to 34.4AH max. lead acid battery (gel type).
Alarm Power:
12VDC, 1.7A max. for each Notification Appliance Circuit.
Aux. Standby Pwr
12VDC, 1A max.
Total Power
Combined auxiliary standby and alarm currents must not exceed 2.3A.
Standby Time:
24 hours with 1A aux standby load using 34.4AH battery.
Fusing:
Battery input, auxiliary and Notification Appliance Circuits are protected using PTC
circuit protectors. All outputs are power limited.
Main Dialer
Line Seize:
Double Pole
Ringer Equivalence:
0.7B
FCC Registration No.:
AC3-USA-68192-AL-E
TLM Threshold
Good line when tip-to-ring voltage greater than approximately 25V (13 when blue
jumper cut) or when handset current greater than approximately 10mA. Bad line
when both voltage and current below these levels.
Formats:
ADEMCO High Speed, ADEMCO 4 + 2 Express, ADEMCO Low Speed, ADEMCO
Contact ID, Sescoa and Radionics Low Speed
Compatible Receivers
7810iR-ent
MX8000
5140DLM BACKUP DIALER MODULE
Physical:
2.75”H X 4”W X 1”D
Mounts on VISTA-128FBP main PC board shield using standoffs supplied.
Connects to VISTA-128FBP main PC board J3 header using ribbon cable supplied.
FCC Registration:
AC3-USA-62628-MO-N
Summary of Contents for VISTA-128FBP
Page 2: ......
Page 8: ...viii ...
Page 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Page 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Page 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Page 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Page 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...