Section 4 – Programming
4-7
Type 14: CO Detector Alarm
Sends a report to the central station and displays a CO
text message at the keyboard. Upon a CO alarm only
the keypad’s sounder will annunciate. The external bell
will not sound at all.
Type 16: Fire with Verification
Provides a fire alarm when there is a short circuit, and
a trouble condition when there is an open circuit. An
initial short results in a 7-second smoke detector power
reset. Any subsequent short within 90 seconds causes a
fire alarm. This type is always active and can only be
bypassed by the Installer code or the Master code, (field
3*85).
Type 17: Fire Waterflow
Provides a trouble condition on open circuit and an
alarm on a short circuit that remains longer than the
programmed time delay (fields 3
✳
16 and 3
✳
18). The
alarm can be silenced by either an entry of
User Code
+ OFF
or when the zone restores (field 3
✳
14). This type
is always active and can only be bypassed by the
Installer code or the Master code, (field 3
✳
85).
Type 18: Fire Supervisory
Provides a supervisory response on a short circuit. Open
circuit can be programmed for either a trouble or
supervisory response (field 3
✳
13). This type is always
active and can only be bypassed by the Installer code or
the Master code, (field 3
✳
85).
Type 19: 24-Hour Trouble
Provides a trouble response on a short or open circuit.
No alarm sounders are activated.
Type 20: Arm-STAY (5800 Series devices only)
Causes the system to arm in the STAY mode when the
zone is activated.
Type 21: Arm-AWAY (5800 Series devices only)
Causes the system to arm in the AWAY mode when the
zone is activated.
Type 22: Disarm (5800 Series devices only)
Causes the system to disarm when the zone is
activated.
Type 23: No Alarm Response
Used on a zone when an output relay action is desired,
but with no accompanying alarm (e.g., for lobby door
access).
Type 27: Access Point – Not Used
Type 28: Main Logic Board (MLB) Supervision – Not
Used
Type 29: Momentary Exit – Not Used
NOTE FOR PANIC KEYS: Keypad panic zones share the same
zone response type for all 8 partitions, but panics may be
individually enabled for each partition.
IMPORTANT! FAULT ANNUNCIATION
Polling loop and RF troubles (zones 988, 990, and 997) report as
trouble conditions only, and as such, should be assigned zone
type 19 if annunciation is desired. See
Polling Loop Supervision
and
RF System Operation and Supervision
in
SECTION 3:
Installing the Control
for more information.
Summary of Contents for VISTA-128FBP
Page 2: ......
Page 8: ...viii ...
Page 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Page 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Page 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Page 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Page 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...