![Honeywell VISTA-128FBP Installation And Setup Manual Download Page 39](http://html.mh-extra.com/html/honeywell/vista-128fbp/vista-128fbp_installation-and-setup-manual_153414039.webp)
Section 3 - Installing the Control
3-17
INPUT POLLING LOOP
CONTROL PANEL
EXTENSION POLLING LOOP #1
4297
COMBINED INPUT AND EXTENSION LOOP LIMITS:
• NO MORE THAN 119 DEVICES COMBINED ON THE INPUT LOOP AND EXTENSION LOOP #1. NO MORE THAN 119 DEVICES COMBINED
ON THE INPUT LOOP AND EXTENSION LOOP #2.
•
TOTAL LENGTH OF ALL WIRE RUNS ON THE INPUT LOOP AND EXTENSION LOOP #1 COMBINED CANNOT EXCEED 6400 FT. (3200 FT.
IF USING UNSHIELDED WIRE IN CONDUIT, OR SHIELDED WIRE). TOTAL LENGTH OF ALL WIRE RUNS ON THE INPUT LOOP AND EX-
TENSION LOOP #2 COMBINED CANNOT EXCEED 6400 FT. (3200 FT. IF USING UNSHIELDED WIRE IN CONDUIT, OR SHIELDED WIRE).
•
WHEN USING THE 4297 TO EXTEND THE POLLING LOOPS, FIRE DEVICES MUST BE ON SEPARATE LOOPS FROM BURG DEVICES TO
PROVIDE ISOLATION.
4297
• DO NOT CONNECT 4297 MODULES IN
SERIES (i.e., DO NOT CONNECT ONE
MODULE'S EXTENSION LOOP TO
ANOTHER MODULE'S INPUT LOOP.)
polling_loop-013-V1
TO
BURG
DEVICES
TO
FIRE
DEVICES
EXTENSION POLLING LOOP #2
CLASS B, STYLE 3
CLASS B, STYLE 3
V-PLEX
DEVICE
V-PLEX
DEVICE
2
1
6
7
8
9
2
1
6
7
8
9
TO PANEL AUX POWER
TO PANEL AUX POWER
DO NOT CONNECT
Figure 3-17: Polling Loop Connections Using Multiple Extender Modules
NOTE:
The input loop limits stated in
Figure 3-16
apply to
Figure 3-17
as well.
Wireless Zone Expansion
UL
The 5881ENHC RF Receiver is Listed for Commercial Fire and Commercial Burglary applications. The 5883H is
Listed for Commercial Fire applications only. All other RF receivers are not UL listed for Commercial applications.
The following table lists the receivers that may be used and the number of zones they support.
5800 Series Receivers
Receiver Zones
5881ENHC
up to 128 (use in commercial fire or
burglary applications)
5883H
up to 128 (use in commercial fire
applications)
RF System Operation and Supervision
The 5800 RF system operation has the following characteristics:
•
The receiver responds to a frequency of 345MHz.
•
The receiver has a nominal range of 200 feet.
•
Supervised transmitters send a supervisory signal every 70-90 minutes.
•
Zones 988 and 990 are used to supervise the RF reception of receivers 2 and 1, respectively. The reception is
supervised for the following two conditions:
1.
The receiver goes “deaf” (doesn’t hear from
any
transmitter) within a programmed interval of time (defined by
program field 1*30).
2.
Proper RF reception is impeded (i.e., jamming or other RF interference). The control checks for this condition
every 20 seconds.
Summary of Contents for VISTA-128FBP
Page 2: ......
Page 8: ...viii ...
Page 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Page 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Page 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Page 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Page 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...