background image

Section 5 – Data Field Descriptions 

5-9 

Cross Zoning is designed so that a combination of two zones must be faulted within a 5-minute period of each other to cause 
an alarm on either zone.  This prevents momentary faults from one of the zones from causing an alarm condition.  You can 
select four "sets" of cross-zones (programmed in data fields 1*22, 1*23, 1*24, and 1*25), keeping in mind the following: 

 

Both zones in each set must protect the same area. 

 

Both zones in each set must be in the same partition.

 

Conditions That Affect Cross-Zone Operation 

 

In the event of a continuous fault (lasting at least 5 minutes) on one of the paired zones, a fault on the second zone 
causes an alarm immediately. 

 

If one of the zones in a pair is bypassed or has a zone response type set to 0, the cross-zoning feature does not apply. 

 

Do not cross-zone entry/exit zones with interior follower zones as this will produce unpredictable results. 

 

If a relay is programmed to activate on a fault of one of the zones, the relay activates without the other zone being faulted. 

 

If a relay is programmed to activate on an alarm or trouble, both zones must trip before the relay activates, and both 
zones must restore for the relay to deactivate (if relay is programmed to deactivate on a Zone List Restore). 

 

If the one of the zones trips and the second zone does not trip within the 5-minute period, an “error” message is 
reported to the central station. The Contact ID event code is 378. 

 

FIELD 

TITLE and DATA ENTRIES 

EXPLANATION 

 

 

1*22 

Cross Zoning Pair One 

Enter 001-128 
Enter 000,000 to disable 

Select the first pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm. 

Must be set to “000,000 “for Commercial Fire and Burglary installations. 

 

1*23 

Cross Zoning Pair Two 

Enter 001-128 
Enter 000,000 to disable 

Select the second pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm. 

Must be set to “000,000” for Commercial Fire and Burglary installations. 

 

1*24 

Cross Zoning Pair Three 

Enter 001-128 
Enter 000,000 to disable 

Select the third pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm. 

Must be set to “000,000” for Commercial Fire and Burglary installations. 

 

1*25 

Cross Zoning Pair Four 

Enter 001-128 
Enter 000,000 to disable 

Select the fourth pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm. 

Must be set to “000,000” for Commercial Fire and Burglary installations. 

 

1*26 

Panic Button or Speedkey 

For A, B, C keys: 
00 = panic function 
01-32 = macro number 

For D key: 
00 = to select a macro to execute when key 
is pressed 
01-32 = macro number 

Select for the A, B, and C keys whether the system performs a panic or a 
speedkey function when the key is pressed.  

Select for the D key whether the system performs a specific macro or if the 
user will select a macro when the key is pressed.  

 

 

1*28 

RF Transmitter Low Battery 
Sound 

0 = disarmed state only 
1 = both armed and disarmed states 

Select when the RF transmitter low-battery condition should display and 
audible beep annunciate on the keypad. 
Must be 1 for Commercial Fire and UL Commercial Burglary installations. 

 

1*29 

RF Transmitter Low Battery 
Reporting 

0 = disable 
1 = enable 

If enabled, the system sends a Trouble message for RF transmitter low-
battery condition to the central station. 
NOTE: The Trouble message will be sent for a transmitter supervision failure, 
independent of this selection.   
Must be 1 for Commercial Fire and UL Commercial Burglary installations. 

 

1*30 

RF Receiver Supervision Check-
in Interval 

Enter 02-15 times 2 hours (4-30 hours). 
00 = disable receiver supervision. 

Select the check-in monitoring interval for the RF receiver(s).  

Failure of a receiver to receive any RF signal within the time entered results in 
the activation of the response type programmed for zone 990 for the first 
receiver and zone 988 for the second receiver and their related 
communication reports. 

Maximum is 2 (4 hr) for Commercial Fire and UL Commercial Burglary 
installations. 

 

 

Summary of Contents for VISTA-128FBP

Page 1: ...V VI IS ST TA A 1 12 28 8F FB BP PN N Commercial Fire and Burglary Partitioned Security System with Scheduling Installation and Setup Guide 800 06306 4 10 Rev C ...

Page 2: ......

Page 3: ...rcuit Board 3 3 Installing the Keypads 3 3 Installing External Sounders 3 4 Auxiliary Relay Connections 3 8 Telephone Line Connections 3 9 Main Dialer Connections 3 9 Wiring Burglary and Panic Devices to Zones 1 8 3 10 Installing V Plex Devices 3 14 Wireless Zone Expansion 3 17 Installing Output Devices 3 21 Installing a Remote Keyswitch 3 22 Installing a Remote Keypad Sounder For Commercial Burgl...

Page 4: ...ing On Line with a Control Panel 7 3 Scheduled Download For Burglary Use Only 7 3 Direct Wire Downloading 7 16 Telco Handoff 7 16 SECTION 8 8 1 General Information 8 1 Setting the Time and Date 8 1 SECTION 9 9 1 General Information 9 1 User Codes and Levels of Authority 9 1 Multiple Partition Access 9 2 Adding a Master Manager or Operator Code 9 3 Changing a Master Manager or Operator Code 9 4 Del...

Page 5: ...ommercial Burglary Requirements A 1 UL609 Local Mercantile Premises Local Mercantile Safe Vault A 2 UL365 Police Station Connected Burglar Alarm A 2 UL1610 Central Station Burglary Alarm A 2 APPENDIX B B 1 APPENDIX C C 1 APPENDIX D D 1 TABLE OF CONTACT ID EVENT CODES D 1 Event Log Alpha Descriptors D 2 ...

Page 6: ...ks to Zone 8 3 13 Figure 3 13 Wiring a Normally Closed Sensor Loop for Tamper Supervision 3 13 Figure 3 14 Wiring a Normally Open Sensor Loop for Tamper Supervision 3 14 Figure 3 15 Polling Loop Connections to the Control Panel 3 16 Figure 3 16 Polling Loop Connections Using One 4297 Extender Module 3 16 Figure 3 17 Polling Loop Connections Using Multiple Extender Modules 3 17 Figure 3 18 Installi...

Page 7: ...ies This symbol indicates a critical note that could seriously affect the operation of the system or could cause damage to the system Please read each warning carefully This symbol also denotes warnings about physical harm to the user ZONE PROG 1 YES 0 NO 0 Many system options are programmed in an interactive mode by responding to alpha keypad display prompts These prompts are shown in a single li...

Page 8: ...viii ...

Page 9: ... trouble Programming Field Settings for UL864 Compliance NOTICE TO USERS INSTALLERS AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product incorporates field programmable software In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL864 certain programming features or options must be limited to specific...

Page 10: ...le 1 enable Must be set to 0 disable 56 DYNAMIC SIGNALING DELAY Y Enter 00 15 times 15 seconds Must be set to 6 90 seconds 77AUTO TROUBLE RESTORE Y 0 disable 1 enable Must be set to 1 enable 80 ZONE TYPE RESTORES FOR TYPES 9 10 14 N 0 disable 1 enable Must be set to 1 enable for zone type 9 1 12 PROGRAM NOTIFICATION SIGNAL Y 0 no 1 yes Must be set to 1 yes 1 13 SYSTEM SENSOR REVERSING RELAY N 0 us...

Page 11: ...BLE DOWNLOAD CALLBACK N 0 callback required 1 no callback required Must be set to 0 callback required 1 57 5800 RF BUTTON GLOBAL ARM N 0 disable 1 enable Must be set to 0 disable 1 58 5800 RF BUTTON FORCE ARM N 0 disable 1 enable Must be set to 0 disable 1 60 ZONE 5 AUDIO ALARM VERIFICATION N 0 disable 1 enable Must be set to 0 disable 1 69 PRINTER TYPE N 0 parallel printer 1 serial printer Not us...

Page 12: ...3 FIRE SUPERVISORY RESPONSE TO OPEN SHORT APPLIES TO ZONE TYPE 18 N 0 Trouble on open Supv on short 1 Supv on open Supv on short Must be set to 0 3 14 WATERFLOW ALARM SILENCE OPTION N 0 Silenced by User Code OFF 1 Silenced when zone restores Must be set to 0 Silenced by User Code OFF 3 16 DELAY FOR ZONE TYPES 17 18 Waterflow Supervisory N Enter 01 15 times 2 seconds Enter 00 for no delay Must be s...

Page 13: ...s At least 30 Seconds 10 Exit Delay 1 03 15 multiplied by 15 seconds 60 Seconds 60 Seconds 11 Entry Delay 2 02 15 multiplied by 15 seconds 00 240 sec 4 minutes 30 Seconds At least 30 Seconds 12 Exit Delay 2 03 15 multiplied by 15 seconds 60 Seconds 60 Seconds 28 Power Up in Previous State 0 no 1 yes Yes Yes 57 Dynamic Signaling Priority 0 primary dialer 1 Communicator as first reporting destinatio...

Page 14: ... Tamper Option Fire Alarm Verification For Zone Response Type 16 Fire tamper selection must be set to 0 Disabled Enabled unless sensors can self verify Exit Time and Progress Annunciation Disable for Remote Arm Not Evaluated for SIA CP 01 Always Enabled Enabled Enabled Cancel Window 5 minutes Enabled Not required to be programmable Cancel Annunciation Keypad displays Alarm Cancel when report is re...

Page 15: ...tput is silent and the keypad does not display or sound the alarm Provides three keypad panic keys 1 A B and 3 C Full Status Remote Interactive Service Peripherals Devices Supports up to 31 addressable devices keypads RF receivers relay modules etc Supervises devices keypads RF receivers and relay modules and individual relays up to 32 as well as system zones RF receivers and keypad panics Provide...

Page 16: ...es an End User Output Programming Mode allowing the user to control outputs System Communication Provides supervision of the phone lines main and backup Supports the 5140DLM optional backup dialer for the second phone line Supports ADEMCO Contact ID ADEMCO High Speed ADEMCO Express and 3 1 4 1 and 4 2 ADEMCO and Sescoa Radionics Low Speed formats The system is shipped defaulted for Contact ID comm...

Page 17: ...le and supervisory conditions to automatically clear from the display when the zone returns to the ready normal state entry of Code OFF is not required Provides Maintenance Signal support for certain smoke detectors 5192SD 5192SDT 5193SD 5193SDT At least one 2 line alpha keypad 6160 6160CR 2 must be connected to the system for programming if you are using keypad programming and must remain connect...

Page 18: ...UT POLLING NOTES 1 2 3 29 28 BLACK RED YELLOW DATA GREEN DATA COMMUNICATORS 7845i ent 4204CF RF RECEIVER DO NOT CONNECT IF USING OPTIONAL AUX POWER BLACK RED BLACK RED BLACK RED YELLOW DATA GREEN DATA BLACK RED YELLOW DATA GREEN DATA 4190SN 4193SN BLACK RED 4101SN 5192SDT 5193SDT 4208SN 4208SNF 4208U 4204 BURGLARY KEYPAD 6160 VPLEX VSI OUTPUT POLLING INPUT POLLING PIR BLACK RED BLACK RED 4193 4208...

Page 19: ...user must be enabled for Global Arming for those partitions when entering user codes A user with access to more than one partition multiple access can log on to one partition from another partition s keypad provided that program field 2 18 Enable GOTO is enabled for each partition he she wants to log on to from another A partition can be selected as a common lobby partition and other partitions ca...

Page 20: ...f any faults exist in the lobby partition or if another partition that affects the lobby is disarmed the lobby cannot be armed and the message UNABLE TO ARM LOBBY PARTITION is displayed You cannot select a partition to arm the lobby unless it has first been selected to affect the lobby Do not enable field 1 19 without enabling field 1 18 The following chart sums up how the common lobby partition w...

Page 21: ...ion is automatic as described by fields 1 18 and 1 19 Other Methods of Arming Disarming Common Lobby logic remains active when arming or disarming a partition that affects and or arms the common lobby in one of the following manners Quick Arm Keyswitch Wireless Button Wireless Keypad Arming Disarming Remotely If a user arms or disarms remotely through Compass downloading software the lobby does no...

Page 22: ... LED on a Master keypad is lit only if all partitions have been armed successfully The Ready LED is lit only if all partitions are ready to arm Neither LED is lit if only some partitions are armed and or only some partitions are ready Press 0 or 9 to return to the master partition Otherwise if no keys are pressed for 2 minutes the system automatically returns to the master partition The sounder on...

Page 23: ...positioned insert supplied lock clip on the inside of the cabinet into the slots on the lock cylinder Use ADEMCO Lock N6277V1 and Lock Clip P3422 2 supplied CABINET DOOR BOTTOM LOCKED UNLOCKED cab_lock_snap 001 V0 ADEMCO ADEMCO PUSH SNAP TAB SNAP TAB PUSH ON LOCK UNTIL IT IS SEATED SECURELY STEP 2 STEP 1 CHECK POSITION Figure 3 1 Installing the Lock Mercantile Premises Listing Guidelines The panel...

Page 24: ... as well as an additional Listed tamper switch must be installed on the cabinet backbox to protect the cabinet from being removed from the wall These devices must also be connected to zone 6 Commercial Fire Guidelines For Commercial Fire installations the following requirements apply See Figure 3 3 System components mounted inside the cabinet must be placed so that all power limited wiring is sepa...

Page 25: ...ads addresses 00 30 may be used you may need to use an auxiliary power supply if the 1A aux output is exceeded Use a 2 line alpha display 6160CR 2 for fire only or 6160 for burglary only To wire the keypads perform the following steps Step Action Determine wire gauge by referring to the Wire Run Length Gauge table below Wire Run Length Gauge Table Wire Gauge Length 22 gauge 450 feet 20 gauge 700 f...

Page 26: ...ng to the keypad s instructions Set an alpha keypad for address 00 and other keypads for higher addresses 00 and 01 are enabled in the system s default program Any keypads set for address 02 and above will appear blank until they are enabled in the system s program Each keypad must be set for a different address Do not set any keypads to address 31 nonaddressable mode They will interfere with othe...

Page 27: ...e wired to a Sync Module if more than one device is used Follow instructions provided with Sync Module Be sure to use the compatible Sync Module for the Alarm Indicating Device selected MANUFACTURER SYNC MODULE MODEL NUMBER GENTEX AVSM SYSTEM SENSOR MDL WHEELOCK DSM UL All visual notification appliances within the same physical area must be synchronized The bell outputs are listed as Special Appli...

Page 28: ...a Red SYSTEM SENSOR PC4RH 4 Wire Ceiling Mount Horn Strobe 12 24V Standard Candela Red Outdoor SYSTEM SENSOR PC4RK 4 Wire Ceiling Mount Horn Strobe 12 24V High Candela Red Outdoor SYSTEM SENSOR PC4RHK 4 Wire Ceiling Mount Horn Strobe 12 24V Standard Candela White SYSTEM SENSOR PC4W 4 Wire Ceiling Mount Horn Strobe 12 24V High Candela White SYSTEM SENSOR PC4WH 2 Wire Wall Mount Strobe 12 24V Standa...

Page 29: ...2 24V PC2RHK 15 Temporal High 10 System Sensor Horn Strobe12 24V PC2W 15 Temporal High 10 System Sensor Horn Strobe12 24V PC2WH 15 Temporal High 10 System Sensor Horn Strobe12 24V PC4R 15 Temporal High 10 System Sensor Horn Strobe12 24V PC4RH 15 Temporal High 10 System Sensor Horn Strobe12 24V PC4RK 15 Temporal High 10 System Sensor Horn Strobe12 24V PC4RHK 15 Temporal High 10 System Sensor Horn S...

Page 30: ...EOUT 10 9 AUX PWR 1 GROUND POLE N O N C CAN DRAW POWER FROM AUX PWR 1 OUTPUT OR FROM SEPARATE SUPPLY ALARM Figure 3 8 Wiring Auxiliary Relay for Alarm Activation Trouble Supervisory Activation 3 61 0 Steady activation in response to any zone or system related trouble condition or to any fire supervisory condition The auxiliary relay remains activated until all fault conditions have been corrected ...

Page 31: ...e RJ31X cable supplied 3 Connect the backup dialer to the J3 connector on the main PC board using the ribbon cable supplied with the module 4 Connect the earth ground screw on the 5140DLM to the earth ground terminal 30 on the main PC board using 16AWG wire 5 If the dialer output is connected to telephone lines that have a telephone company MTU installed cut the blue jumper on the 5140DLM PC board...

Page 32: ...ammed Wiring Burglary and Panic Devices to Zones 1 8 The maximum zone resistance is 100 ohms for zones 1 2 and 8 and 300 ohms for all other zones excluding the 2K EOL resistor To wire burglary and panic devices to zones 1 8 connect sensors contacts to the hardwire zone terminals 15 through 27 Connect N C and N O devices as follows Connect N C devices in series with the high side of the loop The 2K...

Page 33: ...eeding the output s rating 1A Auxiliary power to 4 wire smoke detectors is not automatically reset after an alarm and therefore must be momentarily interrupted using the auxiliary relay Compatible 4 Wire Smoke Detectors Use any UL Listed 4 wire smoke detector that is rated for 12VDC operation and that has alarm reset time not exceeding 6 seconds Some compatible 4 wire smoke detectors are listed be...

Page 34: ...RMINALS e g 4208SNF 12 11 10 9 N O POLE N C Aux Pwr 1 CONTROL PANEL SHOWN POWERED RELAY OPENS WHEN POWER IS LOST AUXILIARY RELAY 8 7 Aux Pwr 4_wiresmk 005 V0 Figure 3 11 4 Wire Smoke Detectors Zone 6 Tamper Configuration Zone 6 may be used as a tamper loop for the Vista 128FBPN Cabinet Door Tamper Switch Assign zone 6 to a burglary partition Program it for day trouble night alarm zone type 5 when ...

Page 35: ...d to monitor for either an open condition or a short condition of a tamper switch on zones 1 8 End of line supervision is required for this option Wiring a Tamper Switch to Zones 1 8 The wiring of the tamper switch depends on whether the tamper switch and the sensor are normally open or normally closed If you are using a normally closed sensor the tamper switch must be normally open Refer to Figur...

Page 36: ... from the power source 1 Do not run polling loop wires within 6 of AC power telephone or intercom wiring The polling loop is carrying data between the control panel and the devices interference on this loop can cause an interruption of this communication The polling loop can also cause outgoing interference on the intercom or phone lines If this spacing cannot be achieved shielded wire must be use...

Page 37: ...Sens or Low Sens condition To install polling loop devices perform the following steps Step Action 1 Select devices from the list of compatible devices shown previously 2 Set the DIP switches in the device if required Refer to the device s instructions for the DIP Switch Tables 3 Mount each device in the desired location Refer to the device s instructions Run wires from the control panel to each d...

Page 38: ...run length and or to provide individual electrically isolated polling loops Refer to Figures 3 16 and 3 17 to follow DO NOT use the 4197 Polling Loop Extender module with the VISTA 128FBPN Be sure to include the total current drawn on the polling loop when figuring the total auxiliary load on the panel s power supply CONTROL PANEL INPUT POLLING LOOP CLASS B STYLE 3 EXTENSION POLLING LOOP 4297 PANE...

Page 39: ...ing Loop Connections Using Multiple Extender Modules NOTE The input loop limits stated in Figure 3 16 apply to Figure 3 17 as well Wireless Zone Expansion UL The 5881ENHC RF Receiver is Listed for Commercial Fire and Commercial Burglary applications The 5883H is Listed for Commercial Fire applications only All other RF receivers are not UL listed for Commercial applications The following table lis...

Page 40: ... each other as well as from the control panel and remote keypads b Each receiver must be set to a different device address The receiver set to the lower address is considered the 1st RF receiver for supervisory purposes c The House IDs must be the same d Using two receivers does not increase the number of transmitters the system can support 127 zones using the 5881ENHC or 5883H Installation and Se...

Page 41: ... IN A SEPARATE CABINET SEE RECEIVER S INSTRUCTIONS FOR DETAILS MOUNTING HOLES INSERT IN RIGHT HAND TERMINALS CIRCUIT BOARD DIP SWITCH YELLOW RED BLACK GREEN INTERFERENCE INDICATOR LED WIRING OPENING PLUG SOCKET ANTENNAS 5881 001 V0 Figure 3 19 5881ENHC 5883 RF Receiver cover removed 5800 Series Transmitter Setup Transmitters have built in serial numbers that must be enrolled in the system using th...

Page 42: ...R Unsupervised Button RF These send only fault signals They do not send low battery signals until they are activated The transmitter may be carried off premises Not applicable in Commercial installations Transmitter Battery Life Batteries in the wireless transmitters may last from 4 to 7 years depending on the environment usage and the specific wireless device being used Factors such as humidity h...

Page 43: ...tions the 4204CF cannot be used to drive sounders in the same physical area as sounders connected to the alarm outputs of the control panel Output devices are not intended for overriding automatic building and fire functions To install the relay modules see Figures 3 20 and 3 21 and perform the following steps Step Action 1 Set the 4204 or 4204CF s DIP switches for a device address 01 15 Do not us...

Page 44: ...the actual external contact wiring Form C relay contacts rated at 2A 28VAC VDC with contact supervision One class B style B EOLR supervised auxiliary input zone Operating power and communication with control panels via the V Plex polling loop Electronics mounted in a small plastic case with tamper protected cover NOTE If Fire devices are used on the polling loop no more than 10 ten 4101SNs may be ...

Page 45: ... ARMED RED TO ZONE 8 TERM 27 TO OUT 5 J2 PIN 6 TO ZONE 7 TERM 25 TO ZONE 7 ZONE 8 TERM 26 TO GND J2 PIN 8 TO OUT 1 J2 PIN 7 4146_keyswitch 001 V0 2000 OHMS EOLR 2000 OHMS 820 OHMS 820 OHMS TAMPER SWITCH N C LOCK SWITCH N O Figure 3 22 Remote Keyswitch Wiring Installing a Remote Keypad Sounder For Commercial Burglary use only An optional Amseco PAL 328N Piezo Sounder can be used to duplicate the so...

Page 46: ... of how the Dynamic Signaling feature functions If Priority 57 is And message is Then Acknowledged before delay expires Message is removed from queue and no message is sent to communications device Primary Phone No 0 Not acknowledged before delay expires Message is sent to both the Primary Phone No and communications device Acknowledged before delay expires Message is removed from queue and no mes...

Page 47: ...rupt the internal CRC is bad NOTES Items 2 and 3 require factory service Items 4 and 5 could be the result of a bad or low battery If the item 6 message appears check the antenna connection and cable if they are secure factory service is required All these messages are displayed in conjunction with the CHECK 8xx message which indicates a trouble on the address to which the communications device is...

Page 48: ...pplications Use care to keep 18VAC wiring separated from all other wiring inside the control panel s enclosure This must be done by running non power limited 18VAC wiring into the control panel s enclosure via one of the knockouts on the left hand side and then tie wrapping these wires to the tie wrap loops located near the knockout Earth Ground Connections In order for the lightning transient pro...

Page 49: ...mA then a 4297 Loop Extender Module can be used This module is powered from the panel s auxiliary power and provides a separate polling loop output which can support an additional 128mA load Note that the total number of points connected to the panel cannot exceed 119 2 In Worksheet 2 enter devices used on Auxiliary Power 1 Calculate standby and alarm currents then add to get Auxiliary Power 1 cur...

Page 50: ...et the Bell 2 Output current subtotal Worksheet 5 Bell 2 Output Current Load Total Current Device Model Device Current X of Units Standby Alarm XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX Bell 2 Output Subtotal terminals 5 6 1 7A max 6 In Worksheet 6 enter the total calculated subtotals of all listed outputs from Worksheets 1 through 5 then add to get the combined current Worksheet 6 Total VISTA 128...

Page 51: ...ttery model number A dual battery harness is supplied that allows two batteries to be wired in parallel for increased capacity Using the total calculated from Worksheet 6 calculate the battery capacity required for the installation Worksheet 7 Battery Capacity Calculation Worksheet Capacity Formula Calculated Value Standby Capacity Total standby current X 24 hours X 1 1 contingency factor Alarm Ca...

Page 52: ...NOTE WHEN CONNECTING BATTERIES IN PARALLEL USE BATTERIES FROM THE SAME MANUFACTURER AND WITH THE SAME VOLTAGE AND CAPACITY RATING USE BATTERIES WITH APPROXIMATELY SAME AGE AND STATE OF CHARGE USE CABLES PROVIDED AND OBSERVE POLARITY IT IS RECOMMENDED THAT ALL BATTERIES BE REPLACED AT SAME TIME EVEN IF ONLY ONE BATTERY HAS BECOME WEAK AS LONG AS ONE GOOD BATTERY REMAINS CONNECTED THE ONCE PER 60 SE...

Page 53: ...nces to the next field SUMMARY OF DATA FIELD PROGRAMMING COMMANDS 91 Select partition for programming partition specific fields 92 Display the software revision level of the control panel 93 Enter Menu mode programming 94 Go to next page of fields 99 Go back to previous page of fields or exit Programming Mode with no installer code lockout 98 Exit Programming Mode with Installer Code lockout Movin...

Page 54: ...lowing Step Action 1 Enter Program Mode Installer Code 8 0 0 0 2 Press 91 which will prompt you for the partition number desired 3 Enter a partition specific field number e g 09 to begin programming When the first field s entry is completed the next partition specific field is automatically displayed When all partition specific fields are programmed the system returns to the global programming fie...

Page 55: ...For programming the following Alarm report codes for zones Restore and supervisory codes All other system report codes ALPHA PROG 1 YES 0 NO 0 For entering alpha descriptors for the following Zone Descriptors Default Screen Custom Words Partition Descriptors DEVICE PROG 1 YES 0 NO 0 For defining the following device characteristics for addressable devices including keypads RF receivers 5881ENHC ou...

Page 56: ...rm applications 999 Panic Do not use in Fire Alarm applications Zone Defaults Zone Zone Type Zone Zone Type 001 09 800 830 00 002 09 970 19 003 03 971 974 19 004 03 975 00 005 03 988 990 00 006 03 992 N A 007 03 995 00 008 03 996 00 009 128 00 997 19 601 632 00 999 06 NOTES Zone 992 is the Duress zone Programming of the zone response type is not applicable This zone requires only the report code p...

Page 57: ... 10 10 00 63 14 00 116 03 00 11 11 00 64 15 00 117 04 00 12 12 00 65 01 00 118 05 00 13 13 00 66 02 00 119 06 00 14 14 00 67 03 00 120 07 00 15 15 00 68 04 00 121 08 00 16 01 00 69 05 00 122 09 00 17 02 00 70 06 00 123 10 00 18 03 00 71 07 00 124 11 00 19 04 00 72 08 00 125 12 00 20 05 00 73 09 00 126 13 00 21 06 00 74 10 00 127 14 00 22 07 00 75 11 00 128 15 00 23 08 00 76 12 00 24 09 00 77 13 00...

Page 58: ...e zone is faulted and the system is armed in the AWAY STAY INSTANT or MAXIMUM mode During the disarmed state day the system annunciates a latched trouble sounding from the keypad and a central station report if desired Assign this zone type to a zone that contains a foil protected door or window such as in a store or to a zone covering a sensitive area such as a stock room or drug supply room It c...

Page 59: ...her a trouble or supervisory response field 3 13 This type is always active and can only be bypassed by the Installer code or the Master code field 3 85 Type 19 24 Hour Trouble Provides a trouble response on a short or open circuit No alarm sounders are activated Type 20 Arm STAY 5800 Series devices only Causes the system to arm in the STAY mode when the zone is activated Type 21 Arm AWAY 5800 Ser...

Page 60: ...ain within the receiver s range Type 04 Unsupervised RF UR Select for 5800 Series transmitters that will not be supervised for check in signals The transmitter may therefore be carried off premises Type 05 Unsupervised Button RF BR Select for 5800 Series transmitters specifically designed for this input type These transmitters send only fault signals They do not send low battery signals until they...

Page 61: ... installations See Output Programming in the Programming Guide for a detailed explanation Programming for Communicator Program the communications device in Device Programming in the 93 Menu Mode Programming Program field 56 Selects the time the panel should wait before it attempts to send a message to the second destination Program field 57 Selects the initial reporting destination for messages Pr...

Page 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...

Page 63: ...ter the Program Mode from the keypad This code cannot be used to disarm the system if it isn t used to arm the system This code cannot be used to re enter Program Mode if Program Mode is exited by the 98 command 04 Enable Random Timers For Partitions 1 8 0 disable 1 enable If enabled the activation time of the window is randomized up to 30 minutes and is initialized by either of two methods User C...

Page 64: ...tallations SIA Guidelines The entry delay time and Abort Window field 88 combined cannot exceed 60 seconds 12 Exit Delay 2 partition specific Enter 03 15 multiplied by 15 seconds Exit Delay 2 is used for a secondary door requiring a longer delay than those assigned to Exit Delay 1 NOTE The delay may not exceed 60 seconds for UL installations The delay must be set for a minimum 60 seconds for SIA i...

Page 65: ...allows triggering of the voltage output 3 on Pin 3 of the J2 header to include zone response type 8 24 hr auxiliary 26 Intelligent Test Report 0 disable 1 enable If enabled no test report is sent if any other type of report was sent since the last test report If disabled test reports are sent at the set intervals regardless of whether or not any other report has been sent Must be 0 for Commercial ...

Page 66: ...ssful or if split dual reporting is desired Do not fill unused spaces NOTE If this field is programmed a secondary subscriber account number field 90 must also be programmed 35 Download Phone Number Enter 0 9 11 for 12 for 13 for a 2 second pause Enter the downloading phone number up to 17 digits Do not fill unused spaces NOTE This field is applicable only if downloading is utilized 36 Download ID...

Page 67: ... 1 Contact ID 2 ADEMCO High Speed 3 ADEMCO Express Enter the reporting format for the primary telephone number 46 Low Speed Format Primary 0 ADEMCO Low Speed 1 Sescoa Radionics Enter the low speed format for the primary telephone number 47 Secondary Format 0 Low Speed 1 Contact ID 2 ADEMCO High Speed 3 ADEMCO Express Enter the reporting format for the secondary telephone number 48 Low Speed Format...

Page 68: ...cations device does not have enough time to sent the acknowledgement back to the panel therefore the report would be sent out via the dialer If the acknowledgment is received before the delay time expires no message is sent to the second destination 57 Dynamic Signaling Priority 0 Primary Dialer 1 Communicator Select the initial reporting path for central station messages NOTE Must be set to 0 for...

Page 69: ...enable any of the panics to report make sure field 22 is programmed correctly for each partition 87 Entry Warning partition specific 0 3 short beeps 1 slow continuous beeps Select the type of warning for the entry delay period 88 Abort Window partition specific 1 15 seconds 2 30 seconds 3 45 seconds The Abort Window exists for all non fire zones All non fire alarm reports are NOT transmitted to th...

Page 70: ...r reversing relay Not Used 1 15 Cancel Verify 0 disable 1 enable alarm output pulse upon kissoff of Cancel report NOTE Field 1 52 must be enabled to send a Cancel report to the central station 1 17 Lobby Partition 0 none 1 8 partition number Select the Common Lobby Partition 1 18 Affects Lobby partition specific 0 disable 1 enable If enabled causes lobby partition to disarm when this partition dis...

Page 71: ...alarm Must be set to 000 000 for Commercial Fire and Burglary installations 1 24 Cross Zoning Pair Three Enter 001 128 Enter 000 000 to disable Select the third pair of cross zones which must both be faulted within a 5 minute period to cause an alarm Must be set to 000 000 for Commercial Fire and Burglary installations 1 25 Cross Zoning Pair Four Enter 001 128 Enter 000 000 to disable Select the f...

Page 72: ... Not Used 1 42 Call Waiting Defeat 0 disable 1 enable If enabled the system defeats Call Waiting on the first outgoing call attempt to both the primary and secondary numbers NOTES After the panel s initial call to report the alarm the panel may attempt to make an additional call perhaps for a cancel or a zone restoral If Call Waiting is not defeated an operator at the central station attempting to...

Page 73: ...or ULC applications 1 60 Zone 5 Audio Alarm Verification 0 disable 1 enable If enabled zone 5 is used for 2 way audio AAV Must be set to 0 for UL commercial fire and burglary installations NOTE Zone 5 cannot be used as protection zone 1 61 Abort Verify 0 disable 1 enable If enabled and an alarm occurs on a non fire zone the system displays ALARM ABORTED if a user enters the code off sequence durin...

Page 74: ...0 12 in which daylight saving time starts and ends Enter 00 00 if daylight saving time does not apply to the user s region Standard setting for U S is 03 11 2 02 Daylight Saving Time Start End Weekend 0 disable 1 enable Enter the start and end weekends for daylight saving time as follows 1 first 2 second 3 third 4 fourth 5 last 6 next to last 7 third from last Standard setting for U S is 2 1 2 05 ...

Page 75: ...r partition s keypad using the GOTO command NOTE Must be disabled 0 for partition 1 in Commercial Fire installations 2 19 Use Partition Descriptor 0 disable 1 enable If enabled the normal keypad display will include a partition number and 4 digit descriptor 2 20 Enable J2 Triggers for Partition partition specific 0 disable 1 enable If enabled the J2 triggers function for this partition 2 21 Superv...

Page 76: ... silenced when zone restores Select how the Waterflow zone type will be silenced NOTES This feature may be set to 1 only by permission of the local authority For an output of a 4204CF to be silenced when 3 14 1 all Type 17 Waterflow zones activating the output must be put into a Zone List and that Zone List must be the STP condition of the 4204CF fire output In addition to the STP ZL you also need...

Page 77: ...ary phone number is programmed 3 30 Dialer Selection 0 disable 1 enable This field has two entries one for each dialer main and backup Enter 1 if the dialer is being used NOTE If 3 30 is disabled 0 0 the panel does not report at all via communications device 3 31 Backup Dialer TouchTone or Rotary 0 rotary 1 touchtone Select the dialing method for the backup dialer 3 50 Zone Type Restore Enables fo...

Page 78: ...silenced by User Code OFF 2 smoke detector reset 3 battery save 4 alarm silenced by User Code 67 Select the condition that will trigger the auxiliary relay NOTES Select 4 for applications requiring independent resetting of the relay Smoke detector reset triggers the relay momentarily approximately 6 seconds on the second User Code OFF entry Battery save is used to disconnect power from non critica...

Page 79: ...uto Arm The warning can be set from 1 to 15 minutes prior to the arming in partition specific program field 2 06 During this period the keypad beeps every 15 seconds and displays AUTO ARM ALERT During the last 60 seconds the keypads beep every 5 seconds The panel arms at the conclusion of the Auto Arm Warning period Extend Closing Window A user can manually delay the arm closing time window by 1 o...

Page 80: ...hin 30 minutes after the end of the time window The system can perform the same actions on a daily basis or can perform an action only once e g turn on the porch light this Wednesday at 8 00 PM The system also provides up to 20 programmable timers available to the end user for the purpose of activating output devices at preset times and days Time Window Definitions Scheduled events are based on ti...

Page 81: ...ide the assigned time window The system keeps a record of all openings closings in its event log If a disarming occurs during a closing window for example a person who arms the system forgets something and has to re enter the Opening report although outside of the opening window will not be sent as long as that disarming occurs within the closing window This option is programmed in partition speci...

Page 82: ... the following 1 Define time windows up to 20 2 Define the daily open close schedules one schedule per day per partition 3 Define the holidays to be used by the system up to 16 4 Define limitation of access times up to eight schedules 5 Define the Time Driven events up to 20 NOTE Temporary schedules are programmed using 81 Menu Mode Use 80 Scheduling Menu Mode to perform the following functions 6 ...

Page 83: ...me Time Windows Programming Enter Scheduling Mode by entering Installer Code 80 The keypad displays the Time Window Programming prompt PROMPT EXPLANATION Time Window 1 YES 0 NO 0 Enter 1 at this main menu prompt to program time windows Time Window 01 20 00 Quit 01 Enter the 2 digit time window number 01 20 to be programmed Press to accept the entry Enter 00 at the Time Window prompt to quit time w...

Page 84: ...hedule is desired for a particular day As the number is keyed in the actual time that has been stored for that window number is displayed as a programming aid Press to accept the entry Mon P1 CL WIND 00 00 00 00 00 Enter the time window number for the displayed day s closing schedule As the number is keyed in the actual time that has been stored for the window number is displayed Press the key to ...

Page 85: ...titions have been assigned The Holiday Number prompt is displayed again Repeat the procedure for each holiday to be programmed Quit 1 YES 0 NO 0 Enter 0 at the Quit prompt to return to the main menu choices and continue programming Enter 1 to quit Scheduling Menu Mode Time Driven Events These schedules are used to activate outputs bypass zones etc based on time There are 20 of these schedules that...

Page 86: ...ng window cannot be extended using the Installer Code 82 Mode Bypass Commands Action Code Action Action Specifier 30 Auto bypass Zone list Zone list 31 Auto unbypass Zone list Zone list Open Close Windows Action Code Action Action Specifier 40 Enable Opening Window by partition Partition s 41 Enable Closing Window by partition Partition s 42 Enable Access Window for access group Access Group 50 Of...

Page 87: ... system then prompts the user to enter the desired action to be taken Enter 00 at the TIMED EVENT prompt to quit the timed event menus and display the Quit prompt 01 ACTION none 00 Enter the action code for this timed event number from the list at the left This could be an output command an arming command or any other Time Driven event Press to accept the entry The prompt for the action specifier ...

Page 88: ... for the time window number is displayed Press to accept entry 01 Active time 0 Enter the activation time from 1 10 listed below As the number is keyed in the activation time is displayed The choices are 1 Trigger at the start of the window 2 Trigger at the end of the window 3 Take effect only for the duration of the window 4 Trigger at both the start and the end of the window Example coffee break...

Page 89: ...the second for a closing time window A user required to follow a schedule would be assigned to an access group of the same number e g schedule 1 group 1 The user s access code is assigned to a group when that user is added to the system If no limitations apply enter 0 Limitation of Access Schedule Worksheet Enter the appropriate time window numbers for each access schedule Acc Mon Tues Wed Thurs F...

Page 90: ...other days of the week When the last day of the week has been programmed the windows for holidays may be entered Hol A1 Window 1 00 00 00 00 00 Enter the first time window number for holidays for this access schedule As the number is keyed in the actual time that has been stored for the window is displayed Press to continue Hol A1 Window 2 00 00 00 00 00 Enter the second time window number for hol...

Page 91: ...r is positioned on the tens of hours digit of the start time of the arm window Enter the hour Press to move to the minutes field The minutes are entered in the same manner Press to move to the AM PM position Pressing any key in the 0 9 range toggles the AM PM indication Repeat the procedure for the stop time entry After the windows for that day have been completed the system prompts for disarm and...

Page 92: ... devices are programmed via 93 Menu Mode 06 ON TIME 07 00 PM The cursor is positioned on the tens of hours digit of the ON time Enter the desired hour Press to move to the minutes field The minutes are entered in the same manner The AM PM indication is toggled by hitting any key from 0 9 while the cursor is under the AM PM position Press to continue 06 OFF TIME 11 45 PM The cursor positioned on th...

Page 93: ...nly if the security codes match 3 Data encryption All data that is exchanged between the computer and control is encrypted to reduce the possibility of anyone tapping the line and corrupting data 4 Operator access levels Operators may be assigned various levels of access to the downloader each having its own log on code The access levels allow the operators read write capabilities of the customers...

Page 94: ... 0 9 A key B key C key 2 Sec Pause Do not fill unused spaces Press the key to accept the phone number and exit Press the key to exit without changing any data The system displays the Quit menu prompt Press 1 to exit the Installer Unattended Program Mode or 0 to continue to the next prompt Unattended Acct 1 YES 0 NO 0 Press 1 to enter the unattended account number Unattended Acct 15 15 15 15 Enter ...

Page 95: ...control but are inactive during actual uploading or downloading sessions For IP ECP downloading all reports can be transmitted while an up load download on line session is active To download a control without programming any information perform the following steps Step Action 1 Enter the Installer Code 5 The panel temporarily enables a ring count of 5 and sets the Download Callback option to 1 cal...

Page 96: ...ent than those shown in the 4100SM Installation Instructions See Figure 7 1 for the correct connections In addition in place of the green wire referred to in step 2 of the IN CASE OF DIFFICULTY section of the 4100SM Instructions use the violet wire instead Connector J2 on the main PC board see the Summary of Connections diagram on the inside back cover of this manual is intended to be interfaced t...

Page 97: ...lculated based on the date entered Time and date entries are made by simply entering the appropriate hour minute month day and year Press to move the cursor to the right of the display to the next position Press to move the cursor to the left of the display to the previous position 2 Enter the correct hour Then press to move to the minutes field 3 Enter the correct minutes Press to move to the AM ...

Page 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...

Page 99: ...ode or by Quick Arm Can add delete or change all other codes and can select Open Close reports for any user Is the only code that can be used to enter program mode The Installer Code can be prevented from re entering the Program Mode by exiting using 98 Must program at least one Master Code during initial installation Master Codes are codes intended for use by the primary user s of the system Leve...

Page 100: ...dds a new user the new user s Open Close reporting is the same as that of the Master or Manager who is adding the user If Open Close reports are required to be selectable by the Master or Manager the Installer should assign two Master or Manager user codes one with Open Close reporting enabled and one without Note that Open Close reporting of Quick Arm is enabled if User 002 is enabled for Open Cl...

Page 101: ...Enter 0 8 If access schedules have been programmed this prompt appears Enter the user s access group number 1 8 if this user should have limited access to the system Enter 0 if no access group should be assigned RF Button 0 NO 1 YES Not Used Multi Access 0 NO 1 YES Press 0 NO if the user is to have access to this partition only Press 1 YES if the user is to have access to more than one partition I...

Page 102: ...igher level of authority than the code being changed e g a Manager Code can add an Operator level Code but cannot add a Master or another Manager Code PROMPT EXPLANATION User Number 003 NEW USER The system detects that the user number is already assigned and prompts if this is a new user Press 0 NO The system then confirms that the change is allowed based on authorization level Deleting a Master M...

Page 103: ...e system must be disarmed Keypads display FIRE DRILL ACTIVE while the test is active The test is stopped by entering any user code OFF The system continues to monitor all 24 hour type zones fire panic etc and ends the test if any of these zone types produce an alarm condition This test should be conducted at periodic intervals as determined by the local authority having jurisdiction One Man Fire W...

Page 104: ...test all of the polling loop points that have a zone response type of 9 or 16 For points that must be manually tested fault and reset each fire alarm sensor in turn Each action should cause keypads to beep and fire Notification Appliance Circuits to ding The keypads will display the zone number and the associated alpha descriptor while the zone remains faulted The system automatically issues a smo...

Page 105: ...g OFF If the system has been programmed for silent panic there are no audible alarms or displays A report is sent to the central station however 8 Notify the central station that all tests are finished and verify results with them Testing Wireless Transmitters Transmitter ID Sniffer Mode Use the Transmitter Sniffer Mode to test that transmitters have all been properly programmed If a transmitter d...

Page 106: ...restored Other System Messages Display Description COMM FAILURE Indicates a failure occurred in the telephone communication portion of your system LO BAT Indicates a low battery condition exists in the wireless transmitter displayed Pressing any key silences the audible warning sound SYSTEM LO BAT This indicates that a low battery condition exists with the system s backup battery HSENS Indicates a...

Page 107: ... well as the User Guide supplied In particular explain the operation of each zone entry exit perimeter interior fire etc Be sure the user understands how to operate any emergency feature s programmed into the system Contacting Technical Support PLEASE before you call Technical Support be sure you READ THE INSTRUCTIONS Check all wiring connections Determine that the power supply and or backup batte...

Page 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...

Page 109: ...M Backup Dialer Module 3 When the main dialer is used enable it field 3 30 and connect it to a telephone line Assign a 24 hour trouble response type 19 to system Zone 974 to enable main dialer supervision The control panel will activate the trouble trigger when it detects a main dialer supervision fault 4 When the backup dialer is used install it on the control panel s PCB shield as indicated in t...

Page 110: ...lugged use the supplied disc plugs and carriage bolts 5 Must be used with a Listed burglar alarm sounding device housing Depending on the application a compatible Listed sounding device enclosure may also be required UL365 Police Station Connected Burglar Alarm Follow the instructions for UL609 local installations given above For Systems without Line Security You may use the control panel s main d...

Page 111: ...m on the line notify the telephone company that it has a problem and request prompt repair service The user may not under any circumstances in or out of warranty attempt any service or repairs to the system It must be returned to the factory or an authorized service agency for all repairs FCC PART 68 NOTICE This equipment complies with Part 68 of the FCC rules On the front cover of this equipment ...

Page 112: ...er Equivalence Numbers of all the devices does not exceed 5 AVIS L étiquette d Industrie Canada identifie le matériel homologué Cette étiquette certifie que le matériel est conforme aux normes de protection d exploitation et de sécurité des réseaux de télécommunications comme le prescrivent les documents concernant les exigences techniques relatives au matériel terminal Le Ministère n assure toute...

Page 113: ...artition User Code 0 Panics 1 or A Key Zone 995 or B Key Zone 999 3 or C Key Zone 996 View Downloaded Messages Press 0 for 5 Seconds Display All Zone Descriptors Press for 5 Seconds Additional Commands Display User Self Help Hold Any Key for 5 Seconds Output Device Control Commands Activate Output Device as Programmed User Code 71 Activate Output Device as Programmed User Code 72 Activate Output D...

Page 114: ...VISTA 128FBPN Installation and Setup Guide B 2 Relay Control Commands Activate Relay for Current Partition User Code 0 ...

Page 115: ...tected using PTC circuit protectors All outputs are power limited Main Dialer Line Seize Double Pole Ringer Equivalence 0 7B FCC Registration No AC3 USA 68192 AL E TLM Threshold Good line when tip to ring voltage greater than approximately 25V 13 when blue jumper cut or when handset current greater than approximately 10mA Bad line when both voltage and current below these levels Formats ADEMCO Hig...

Page 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...

Page 117: ...rouble 354 Communication Fail 373 Fire Loop Trouble 374 Exit Error by Zone 378 Cross Zone Trouble Code Definition 380 Trouble global 381 Loss of Supervision RF 382 Loss of V Plex Supervision 383 V Plex Sensor Tamper 384 RF Transmitter Low Battery 385 High Sensitivity Maintenance Signal 386 Low Sensitivity Maintenance Signal 389 Detector Self Test Failed 401 O C by User 403 Power Up Armed Auto Arm ...

Page 118: ...D Disarmed DISARMED REM Disarmed Remotely DISARMED KEY Disarmed Via RF Key DISARM AUTO Auto Disarm CALL BACK Callback Requested CANCEL Cancel DISRMD EARLY Disarmed Early DISRMD LATE Disarmed Late MISSED DISRM Missed Disarm SKED CHANGE Schedule Change ACC SKED CHG Access Control Schedule Change ARM FAILED Failed to Arm DIALER SHUT Dialer Shutdown Alpha Event Description SYSTEM SHUT System Shutdown ...

Page 119: ...Comm Failure from MLB to Module RES MOD Access Control Module Reset ACPT RLY Access Point Relay Supervision Fail SELF MOD Module Self Test Failure Access Control Events ACZN CHG Access Control Zone Change ACS PROG Access Control Program Entry ACS PRGX Access Control Program Exit THRT CHG Access Control Threat Change SYS SHUT System Shutdown SYS RST System Engineer Reset ZN SHUNT Access Control Zon...

Page 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...

Page 121: ... Addressing the Keypads 3 4 ADEMCO 4 2 Express 3 10 ADEMCO 4 2 EXPRESS C 1 ADEMCO 685 receiver 3 10 ADEMCO CONTACT ID C 1 ADEMCO HIGH SPEED C 1 ADEMCO Low Speed 3 10 ADEMCO LOW SPEED C 1 Affects Lobby 2 2 5 8 Agency Statements A 1 Alarm Activation 3 8 Alarm Indicating Devices 3 5 3 7 Alarm Output Supervision 3 5 Alarm Power C 1 Alarm Restore Report Timing 5 7 Allow Disarm Outside Window if Alarm O...

Page 122: ...Data Field Programming Mode 4 1 Daylight Saving Time Start End Month 5 12 Daylight Saving Time Start End Weekend 5 12 Deleting a User Code 9 4 DEVICE PROG 4 3 Dial Tone Detection 5 4 Dial Tone Pause 5 4 Dialer Operation 3 11 Dialer Test 10 1 DIGITAL COMMUNICATOR C 1 DIP Switch Loop DP Type 07 4 8 Direct Wire Downloading 7 4 Disable Download Callback 5 11 Disarm Delay 6 1 Disarm Type 22 4 7 Display...

Page 123: ... Interior w Delay Type 10 4 7 Interior Follower Type 04 4 6 K Keypad Panic Enables 5 2 Keypads 2 1 Keyswitch 3 23 Keyswitch Assignment 5 2 Keyswitch Tamper 3 24 L Limitation of Access 6 2 Limitation of Access Schedules 6 11 Limitation Of Access Schedules Programming 6 12 Line Security A 2 LINE SEIZE C 1 List of Figures vi LO BAT 10 4 Lobby Partition 5 8 Log 1 st Main Signal 5 12 Low Speed Format P...

Page 124: ...mands 6 8 Relay Control Commands B 2 Relay Timeout XXX Minutes 5 11 Relay Timeout YYY Seconds 5 11 Remote Keypad Sounder 3 24 Remote P S Type 13 4 7 REPORT CODE PROG 4 3 Reporting Formats 3 10 Restrict Disarming 6 1 RF Motion 3 21 RF Motion RM Type 02 4 8 RF Receiver Supervision Check in Interval 5 9 RF System Installation Advisories 3 19 RF System Operation and Supervision 3 18 RF Transmitter Che...

Page 125: ...al Mercantile Premises Local Mercantile Safe Vault A 2 UL864 NFPA Central Station and Remote Station Fire A 1 UL864 NFPA Local Fire A 1 UNABLE TO ARM LOBBY PARTITION 2 2 Unattended Download 7 1 Unattended Mode 5 6 Unsupervised Button RF BR Type 05 4 8 Unsupervised RF 3 21 Unsupervised RF UR Type 04 4 8 Use Partition Descriptor 5 13 User Access Codes 9 1 User Code Authority Levels 9 1 User Code Com...

Page 126: ...annot detect motion or intrusion that takes place behind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detection ability Passive Infrared Detectors sense changes in temperature however as the ambient temperature of the protected ar...

Page 127: ...ERIES ALL POWER LIMITED WIRING MUST BE SEPARATED FROM NON POWER LIMITED AND HIGH VOLTAGE WIRING BY 1 4 INCH 6 4 mm For commercial fire bell timeout must be a minimum of 6 minutes Use only 14 22 AWG wire 5 2k EOLR is Ademco Model EOL20 6 No more than one 1 wire per terminal may be connected 4 See instructions on setting addresses for max of keypads and wire run length restrictions 3 2 All zones are...

Page 128: ...Š 800 06306 4 10 Rev C For the latest warranty information please go to www honeywell com security hsc resources wa 2 Corporate Center Drive Suite 100 P O Box 9040 Melville NY 11747 Copyright 2010 Honeywell International Inc www honeywell com security ...

Reviews: