![Honeywell VISTA-128FBP Installation And Setup Manual Download Page 33](http://html.mh-extra.com/html/honeywell/vista-128fbp/vista-128fbp_installation-and-setup-manual_153414033.webp)
Section 3 - Installing the Control
3-11
UL
•
These smoke detectors are UL Listed for use with the VISTA-128FBPN and are the only 2-wire smoke
detectors that may be used.
•
A combination of heat detectors and smoke detectors is not permitted on a zone programmed for fire
verification.
•
Fire installations require the use of a synchronization module to synchronize the sounders and strobes on
the system.
Wiring 2-Wire Smoke Detectors to Zones 1 and 2
2K EOL resistors must be used on fire zones and must be connected across the loop wires of each zone at the
last detector.
To wire 2-wire smoke detectors to zone 1 and/or zone 2, perform the following steps:
Step Action
1
Select 2-wire smoke detectors from the list of compatible detectors.
2
Connect 2-wire smoke detectors across zone 1 (terminals 15 and 16), and/or zone 2 (terminals 17 and 18) as
shown in
Figure 3-10
. Observe proper polarity when connecting the detectors.
3
Connect the EOL resistor at the last detector in the loop across the zone 1 terminals.
The EOL resistor
must be connected across the loop wires at the last detector.
ZONE 1
2-WIRE SMOKE
DETECTOR
SMOKE
2000 OHMS
EOLR
15
16
2_wiresmk-001-V0
Figure 3-10: 2-Wire Smoke Detector on Zone 1 (for zone 2 use terminals 17 and 18)
Using 4-Wire Smoke Detectors on Zones 1-8
You may use as many 4-wire smoke detectors as can be powered from the panel's Auxiliary Power output without
exceeding the output's rating (1A).
Auxiliary power to 4-wire smoke detectors is not automatically reset after an alarm, and therefore must be
momentarily interrupted using the auxiliary relay.
Compatible 4-Wire Smoke Detectors
Use any UL Listed 4-wire smoke detector that is rated for 12VDC operation and that has alarm reset time not exceeding
6 seconds. Some compatible 4-wire smoke detectors are listed below.
DETECTOR TYPE
MANUFACTURER
MODEL #
4-Wire Photoelectric Smoke Detector
DSC
FSA-410B
4-Wier Photoelectric Smoke Detector w/Heat Detector
DSC
FSA-410BT
4-Wire Photoelectric Smoke Detector w/Sounder & Heat Detector
DSC
FSA-410BST
4-Wire Photoelectric Smoke Detector w/Aux. Relay & Heat Detector
DSC
FSA-410BRT
4-Wire Photoelectric Smoke w/Aux. Relay, Sounder & Heat Detector
DSC
FSA-410BRST
End of Line Power Supervision Relay for FSA-410 Series Smoke Detectors
DSC
RM-2
Polarity reversal module for FSA-410 series Smoke Detectors
DSC
PRM-4WC
4-Wire Photoelectric Smoke Detector
System Sensor
4W-B
4-Wire Photoelectric Smoke Detector w/Heat Detector
System Sensor
4WT-B
4-Wire Photoelectric Smoke Detector w/Sounder & Heat Detector
System Sensor
4WTA-B
4-Wire Photoelectric Smoke Detector w/Aux. Relay & Heat Detector
System Sensor
4WTR-B
4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Heat Detector
System Sensor
4WTAR-B
4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Isolated Heat Detector
System Sensor
4WITAR-B
4-Wire Photoelectric Air Duct Smoke Detector, Extended Air Speed Range
System Sensor
DH100ACDCLP
4-Wire Ionization Air Duct Smoke Detector
System Sensor
DH100ACDCI
Summary of Contents for VISTA-128FBP
Page 2: ......
Page 8: ...viii ...
Page 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Page 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Page 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Page 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Page 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...