
V128FBPN-SOC-V1
VIST
A-128FBPN SUMMAR
Y OF CONNECTIONS
TRANSFORMER
W/ENCLOSURE
ADEMCO No.1451
(supplied)
INPUT: 120VAC,
60HZ,
1.0A max. Connect to a
dedicated circuit.
See instructions for
proper earth ground
connections
123456
7
8
9
1
0
30
PROGRAMMABLE
AS KEYSWITCH LOOP
PROGRAMMABLE
AS TAMPER LOOP
2-WIRE GLASS BREAK
DETECTOR LOOP
2k (note 6)
+
Data in
Data out
+
BACK-UP LINE SEIZE
LED (GREEN)
Connect to main PCB
header J3 using ribbon
cable (supplied)
BACK-UP TLM ON HOOK
VOLTAGE THRESHOLD (BLUE)
INTACT: 25V
CUT: 13V
OPTIONAL 5140DLM BACK-UP DIALER MODULE
MAIN PCB SHIELD
BACK-UP PHONE JACK
SEE TELCO
JACK SHOCK
WARNING
BELOW
J2
Make connections using 4142TR cable
VOLTAGE
TRIGGERS
(not supervised)
J3
1 2 3 4 5 6 7 8 9
J4
Make connections using
4142TR cable (supplied)
KEYPAD PORT #2
BELL 1
W1
(WHITE)
BELL 2
W4
(WHITE)
BLK + RED
OPTIONAL REMOVABLE
TERMINAL BLOCK KIT:
ADEMCO NO. 4142BLK
BELL
HORN
BELL
HORN
N.C.
N.O.
N.C.
N.O.
TO OTHER DEVICES
2k
2k 2k
2k
ZONE 4
2k
(NOTE 5)
2k
AC WIRING IS
SUPERVISED
BELL 1
BELL 2
+
+
ALARM POLARITY SHOWN
N.O
.
PO
LE
N.C.
AUX RELAY (FORM C)
programmable response
(not supervised)
Contact Rating:
28VAC/VDC, 2.8A
resistive loads
SPARE AUX
POWR #1
Connect to 12V, 12AH min/34.4AH max
lead acid batteries using cables supplied.
See instructions for required capacity.
Float charging voltage: 13.7VDC. Battery
normally need not be replaced for
at least 3 yrs.
J4 KEYPAD PORT #2
See instr. regarding port #2 use
1. GROUND (to keypad black wire)
4. DATA IN 2 (to keypad green wire)
5. AUX PWR #2 (to keypad red wire)
Rating: 10 - 14 VDC,
400mA max. See note 1
7. DATA OUT 2 (to keypad yellow wire)
W6
(BLUE)
INTERFACE TO 5140DLM
MAIN DIALER ON HOOK
VOLTAGE THRESHOLD
INTACT:25V
CUT: 13V
BACK-UP DIALER EARTH
GROUND SCREW
(wire to main PCB
terminal #30)
J2 VOLTAGE TRIGGERS
See instructions for trigger use and programming
(default functions shown)
1. OUT 4 (SILENT PANIC/DURESS)
2. OUT 7 (TROUBLE)
3. OUT 3 (BURGLARY/AUDIBLE PANIC)
4. OUT 6 (SUPERVISORY)
5. OUT 2 (FIRE)
6. OUT 5 (REMOTE KEYPAD SOUNDER)
7. OUT 1 (OPEN/CLOSE)
8. GROUND
9. IN 1 (N.O. LOOP)
RATINGS: OUT 1, 5, 7:
LOW: 2K TO GROUND
HIGH: 10 - 14VDC, 20mA MAX
OTHER OUTS:
LOW: 1K TO GROUND
HIGH: 10 - 14VDC THRU 5K
Attach 5140DLM module to main PCB shield using
4 standoffs (supplied)
1 2 3 4 5 6 7 8 9
BATTERY TABS
PINS 2, 3, 6, 8 & 9 NOT USED
RJ31X
MAIN
PHONE JACK
BELL OUTPUTS
AUX. RELAY
INPUT
OUTPUT
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM HEAD-
QUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH
THE APPROVAL OF THE LOCAL
AUTHORITY HAVING JURISDICTION.
THE BURGLARY ALARM SIGNAL
SHALL NOT BE CONNECTED TO A
POLICE EMERGENCY NUMBER.
POLLING
LOOP
TO PREVENT
RISK OF
ELECTRICAL
SHOCK,
DISCONNECT
TELCO
JACK BEFORE
SERVICING
THIS PANEL
Connect
RJ31X using
cable supplied.
Supervision is
programmable
OUTPUT: 18VAC
72VA
BL
BL
BLACK
WH
RJ31X
(connect using supplied cable)
Supervision is programmable
EARTH GROUND
• Ratings for zones 1,2:
- 2mA max for all smoke det.
(up to 16 detectors of the type
specified in the instructions can
be used)
- UL compatibility ID: A
TRNSFMR
TEST BURGLARY SYSTEM WEEKLY
The 5140DLM Dialer
Complies with FCC Rules, Part 68
FCC Reg. No.: AC398U-68628-MO-N
Ringer Equivalence: 0.7B
5193SD SMOKE
4208SNF
28
29
4208U
The Main Dialer Complies with
FCC Rules, Part 68
FCC Reg. No.: AC3-USA-68192-AL-E
Ringer Equivalence: 0.7B
FOR DRY, INDOOR USE ONLY
The impedance at which a ground
fault is annunciated is 1,000 ohms
Special Application Circuit
Connect Only Fire Keypads to
AUX PWR # 2.
Maximum Loop Impedance is 1.17 ohms.
Each output is Class B and may be selected for Style Y
supervision or no supervision. (See main PCB jumpers
W1, W4 and #93 Menu Mode.)
FIRE CKTS: Use only devices listed as Special Application
NAC Devices in Installation and Setup Guide. Supervise
using 2k EOLR. Use polarized sounding devices and
backup batteries.
BURG CKTS: Supervision not req'd. EOLRs not req'd.
May use non polarized devices.
1.7A max. See note 1, see instructions for compatible devices.
NOTES
ALL CIRCUITS ARE POWER LIMITED EXCEPT THE OUTPUT
OF THE 1451 TRANSFORMER AND BACKUP BATTERIES.
ALL POWER-LIMITED WIRING MUST BE
SEPARATED FROM NON-POWER LIMITED
AND HIGH VOLTAGE WIRING BY 1/4 INCH
(6.4 mm)
For commercial fire, bell timeout must be a minimum of
6 minutes.
Use only 14-22 AWG wire.
5.
2k EOLR is Ademco Model EOL20.
6.
No more than one (1) wire per terminal may
be connected.
4.
See instructions on setting addresses & for
max # of keypads and wire run length
restrictions.
3.
2.
•
All zones are Class B and provide Style B supervision
• Zone resistance (excluding EOLR):
- Zones 1, 2, 8: 100 ohms max
- Other zones: 300 ohms max
• Zone response: 350 - 500mS (all zones)
This equipment should be installed in accordance with the National Fire Protection Association's Standard 72
(National Fire Protection Assoc., Batterymarch Park, Quincy, MA. 02169). Printed information describing
proper installation, operation, testing, maintenance and repair service is to be provided with this equipment.
This unit includes a Fire Alar
m
V
er
ification f
eature that will result in a dela
y of
the System Alar
m Signal from the indicated Fire Alar
m circuits
. The total dela
y
(Control Unit plus Smok
e Detectors) shall not e
xceed 30 seconds
. No other
Smok
e Detector shall be connected to these circuits unless appro
v
ed b
y the
local author
ity ha
ving jur
isdiction.
COMMERCIAL FIRE AND B
URGLAR ALARM PR
O
TECTED PREMISES CONTR
OL UNIT
W
ARNING:
TYPES OF FIRE SIGNALLING SERVICE:
Manual fire alarm, automatic fire alarm, sprinkler supervisory and waterflow alarm, DACT, Radio Frequency (RF) and Multiplex.
UL Listed local control (non-coded). UL Listed central station and remote station protected premises unit when used with
5140DLM back-up dialer module. Installation limits under jurisdiction of local authority.
2k
2-WIRE SMOKE
DETECTOR LOOP
N.C.
N.O.
SMOKE
2-WIRE SMOKE
DETECTOR LOOP
N.C.
N.O.
+
SMOKE
18
19
17
ZONE 1
ZONE 2
15
11
12
13
14
16
KEYPAD PORT #1
REMOTE KEYPADS:
6160, 6160CR-2,
SEE NOTE 2
Red
Blk
Grn
Yel
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
2k
2k
21
22
20
23
24
ZONE 3
25
27
27
26
GLASS BREAK
ZONE 7
ZONE 8
ZONE 5
ZONE 6
FOR INSTRUCTIONS
SEE 800-06306,
DATED 4/10
WARNING:
ASSEMBLED
IN MEXICO
• Voltage rating, all zones - 12VDC.
• Do not mix fire and burg. sensors on one loop.
N.C. contacts for burg. usage only.
ZONE 1-8 NOTES
Polling Loop: Class B, Style 3.
Polling Loop Ratings:
(supervised) 128mA max. See note 1.
8-11 VDC
20 Ohms Max. Impedance
See instructions for compatible devices and for max
wire run length. Fire and Burglary devices on the
polling loop must be isolated by use of a 4297 or
VSI module. Refer to instructions for specific examples.
- Maximum fire loop capacitance
is 100 uf.
Smok
e Detector
Control Unit Dela
y, Seconds
Circuit (z
one)
Model
Dela
y, Seconds
THE DELAY TIME MARKED ON THE INSTALLED DETECTOR(S) IS TO BE USED.
8 Seconds
8 Seconds
8 Seconds
Zone 2
A
ux Rela
y
Zone 1
BELL CIRCUIT SUPERVISION JUMPERS
DO NOT CUT
NOTE:
J2 Voltage triggers can only be used with the
4146 keyswitch for fire applications. Trigger Wiring
must be run in conduit within 20ft of the Control Panel.
1.
The combined standby current drawn from
aux pwr #1, aux pwr #2 and polling loop
cannot exceed 1.0A (for Canada, 650mA).
The combined alarm current drawn from aux
pwr #1, aux pwr #2, polling loop, bell 1 and
bell 2 cannot exceed 2.3A
(for Canada, 1.95A).
AUXILIARY POWER #1
1.0A MAX (STANDBY) (For Canada 650mA)
1.7A MAX (ALARM) (See Note 1.)
Max. Impedance: 0.6 Ohms
Special Application Circuit.
Fire & Burglary Devices on the ECP Bus
must be isolated using an ECP Isolator.
Refer to Instructions for specific examples.
ECP Bus: Max. Line Impedance: 50 Ohms
Special Application Circuit.
If supervision of the batteries is required, they
should be connected to the Battery Sense
Module. The Battery Sense Module is then
connected to the panel. Refer to the Battery
Sense Module instructions for connections.
7.
(SEE NO
TE 7)
ZONE INPUT SPECIFICA
TIONS
ZONE 8
ZONES 2-7 EOLR CONFIG.
Maxim
um Loop Current (shor
t loop):
7.4mA
Maxim
um Loop
V
oltage (open loop):
13.3VDC
Loop Shor
t:
0V - 1.5V - 300 ohms total resistance)
Loop Nor
mal:
4.2 - 6.8V
, 1.2k - 2.6k
Loop Open:
7.2V - 13.3V
, 3k -
Maxim
um Loop I:
9mA
Maxim
um Loop
V
: 13.3VDC
Loop Shor
t:
0 - 2.2V - (0 - 300 ohms)
Loop Nor
mal:
5 - 9V (0.9k - 3.4k)
Loop Open:
10V - 13.3V
, 3.8k -
ZONE 9
Maxim
um Loop I:
4mA
Maxim
um Loop
V
: 13.3V
Loop Shor
t:
NA
Loop Nor
mal:
0 - 1.5V (0 ohms - 400 ohms)
Loop Open:
5.3V
, 2.2k -
Summary of Contents for VISTA-128FBP
Page 2: ......
Page 8: ...viii ...
Page 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Page 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Page 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Page 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Page 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...