S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
65-0321—01
62
1 DC2500-CE-200R-200-00000-00-0
2 DC3200-CE-200R-210-10000-00-0
3
Low Fire Hold alarm uses setpoint 1 of alarm 2. If this alarm setpoint is disabled (A2S1TY is NONE), then this alarm is disabled.
Algorithm:
CTRALG
PIDA
PIDA
PIDA
PIDA
TIMER
DIS
DIS
DIS
DIS
Output:
OUTALG
CURRENT
CURRENT
CURRENT
CURRENT
Input 1:
IN1TYP
100H
100H
100H
100H
IN1 HI
1200
1200
1200
1200
IN1 LO
-300
-300
-300
-300
Input 2:
IN2TYP
DIS
DIS
DIS
DIS
Control:
LSP’S
1 ONLY
1 ONLY
1 ONLY
1 ONLY
SP TRK
NONE
NONE
NONE
NONE
PWR UP
ALSP
ALSP
ALSP
ALSP
SP Hi
300
300
500
500
SP Lo
0
0
0
0
ACTION
REV
REV
REV
REV
Options:
AUXOUT
DIS
DIS
DIS
DIS
DIGIN1
NONE
NONE
NONE
NONE
DIGIN2
NONE
NONE
NONE
NONE
Communications:
ComADR
20
20
20
20
ComSTA
MODB
MODB
MODB
MODB
BAUD
19.2K
19.2K
19.2K
19.2K
TX_DLY
1
1
1
1
WS FLT
FP B
FP B
FP B
FP B
SDENAB
DIS
DIS
DIS
DIS
UNITS
ENG
ENG
ENG
ENG
Alarms:
A1S1TY
PROC
PROC
PROC
PROC
A1S1VA
300
300
500
500
A1S1HL
HIGH
HIGH
HIGH
HIGH
A1S2TY
NONE
NONE
NONE
NONE
A2S1TY
NONE
PROC3
NONE
PROC3
A2S1VA
NONE
50
NONE
50
A2S1HL
NONE
LOW
NONE
LOW
A2S2TY
NONE
NONE
NONE
NONE
ALHYST
0
0
0
0
ALARM1
NoLATCH
NoLATCH
NoLATCH
NoLATCH
BLOCK
DIS
DIS
DIS
DIS
DIA AL
DIS
DIS
DIS
DIS
Display:
DECMAL
ONE
ONE
ONE
ONE
TUNITS
F
F
F
F
Summary of Contents for S7999D1048
Page 70: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 70 ...
Page 72: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 72 ...
Page 74: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 74 ...
Page 75: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 75 65 0321 01 ...