S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
65-0321—01
28
NOTE: Clicking the Home, Back or Monitor button will
exit Commissioning mode and display the Home
page.
Password
You must enter the R7999 Commission password into the
system (Fig. 47). The password consists of a minimum of four
characters/numbers and a maximum of ten characters/
numbers.
Fig. 47. Commission login.
To change the R7999 Commission password, proceed as
follows:
1.
Select the Set Password button on the Commissioning
Warning screen.
2.
Enter the current password in the
Commission Password
field. (The factory default password is “password”.)
3.
Press
OK.
The system must be successfully connected
in order to change the password.
4.
Enter a new password in the
New Password
field.
5.
Press
OK
.
NOTE: The password is case sensitive. Make sure you
write down your new password before you press
OK
. Once you have pressed this button you
cannot enter the system without the password.
Fig. 48. Commissioning login to set password.
Commission Configuration
The Commission Configuration screen is used to:
• Identify the configuration of the system you want to
commission, for example, dual fuel system with a FGR or a
single fuel system, etc.
• Begin configuration of the actuators.
• Allow the user to set System Parameters.
• Load a curve from the S7999D flash.
• Begin configuration of the modulation curve.
This screen (Fig. 49) selects the type (Base Configuration) of
ControLinks™ Control System to be configured. The Base
Configuration defines the number of actuators connected to the
ControLinks™ controller. After the Base Configuration is
chosen, the corresponding actuators are enabled as Endpoint
Configuration options.
Selecting the Unconfigured Base Configuration sets all the
ControLinks™ Control parameters back to the factory default
settings. All user configurable data stored in the ControLinks™
Control will be deleted by selecting this option. A warning
message is displayed to confirm this selection.
Single Fuel configuration enables the Air and Fuel 1 actuator
buttons in the Endpoint Configuration options. Single Fuel with
FGR enables the Air, Fuel1 and FGR buttons. Dual Fuel
enables the Air, Fuel1 and Fuel2 buttons. Dual Fuel with FGR
enables all four actuator buttons. Begin configuring the
actuators by selecting the enabled buttons.
Summary of Contents for S7999D1048
Page 70: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 70 ...
Page 72: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 72 ...
Page 74: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 74 ...
Page 75: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 75 65 0321 01 ...