S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
69
65-0321—01
Setpoints:
None
APPLICATION NOTE
Application:
Feed Pump
Description:
Monitor digital inputs to start and stop boiler feedwater and to alarm an open circuit on
high water condition.
Digital Inputs:
None
Digital Outputs:
Start-Stop relay (ON when Start boiler in
ON, OFF otherwise)
High Water Alarm (ON when high water
alarm input is ON, OFF when high water
alarm input is OFF)
Analog Inputs:
Level Transmitter
(4-20 mA)
Analog Outputs:
None
Application File:
pump01.nge
Range
0–100%
Controller
Model
DC2500-EB-200R-200-00000-00-0
Algorithm:
CTRALG
ONOFF
TIMER
DIS
Output:
OUTALG
RLY
Input 1:
IN1TYP
4–20
IN1 HI
100
IN1 LO
0
Input 2:
IN2TYP
DIS
Control:
LSP’S
1 ONLY
SP TRK
NONE
PWR UP
ALSP
SP Hi
100
SP Lo
0
ACTION
REV
HYST
0
Options:
AUXOUT
DIS
DIGIN1
NONE
DIGIN2
NONE
Communications:
ComADR
40
ComSTA
MODB
BAUD
19.2K
TX_DLY
1
WS FLT
FP B
SDENAB
DIS
UNITS
ENG
Alarms:
A1S1TY
PROC
A1S1VA
75
A1S1HL
HIGH
A1S2TY
NONE
A2S1TY
NONE
A2S1VA
NONE
A2S1HL
NONE
A2S2TY
NONE
ALHYST
50
ALARM1
NoLATCH
BLOCK
DIS
DIA AL
DIS
Display:
DECMAL
ONE
TUNITS
NONE
Summary of Contents for S7999D1048
Page 70: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 70 ...
Page 72: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 72 ...
Page 74: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 74 ...
Page 75: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 75 65 0321 01 ...