S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
65-0321—01
58
R7999 OUTPUTS AND INPUTS
The current state of the R7999 outputs and inputs are displayed on the Monitor screen for convenience and diagnostics purposes.
The inputs and outputs are defined as follows:
Table 8. Outputs.
Table 9. Inputs.
UDC CONTROLLER APPLICATION
UDC Controller Interface
The UDC controllers interface to the S7999D via the COM 2 port. The following interface requirements must be specified in the
Communications group of the UDC controller.
The Modbus™ address setting in ComADR determines the
UDC controller application type. Careful assignment of
Modbus™ addresses to UDC controllers and S7810M devices
is necessary so that duplicate addresses aren’t used.
The following application notes describe how the UDC
controller is configured to perform different functions in a
burner/boiler system. Using the UDC controller models and
recommended sensor types for each application is critical to
the success of the application. These application notes only
provide an introduction to the setup needed. More detailed
information for UDC controller setup should be obtained from
the appropriate UDC documentation (see Installing the
Hardware).
UDC controller parameters applicable for each application are
listed, and recommended settings for typical variants of the
application are provided.
Abbreviation
Description
Meaning when ON
LCO
Limit Control Output
Limits are satisfied and demand exits. The R7999 is operational and able to move all
actuators.
HFP
High Fire Proved
The R7999 has moved the actuators to the Purge position.
LFP
Low Fire Proved
The R7999 has moved the actuators to the Lightoff position.
Fuel 1
Fuel Select Channel 1 Fuel 1 is selected.
Fuel 2
Fuel Select Channel 2 Fuel 2 is selected.
ALM
Alarm
The system is in an alarm state.
Abbreviation
Description
Meaning when ON
LCI
Limit Control Input
Limits are satisfied and demand is present.
HF
High Fire Input
R7999 is being commanded to drive actuators to the Purge position.
LF
Low Fire Input
R7999 is being commanded to drive actuators to the Lightoff position
MV
Main Valve Input
The main valve input is active. Normally only active during “Run,” and transitional with LF
during lightoff.
Table 10. UDC Controller Communication Interface .
Parameter
Setting
Comment
ComADR
10-19=Stack Temperature
20-29=Water Temperature PID Load Control
30-39=Steam Pressure PID Load Control
40-49=Feed Pump/Level Control
50-59=Steam/Gas Flow Monitor
60-69=Steam/Fuel Oil Flow Monitor
70-79=Thermal Shock
Modbus™ slave address
COMSTA
MODB
Modbus™ communication
IRENAB
ENAB
Enable infrared communication port
BAUD
19.2K
19200 bps
TX_DLY
1
Response delay = 1 ms
WS_FLT
FP B
Floating point data order
SDENAB
DIS
Disable shed functionality
UNITS
EGR
Data specified in engineering units
CSRATIO
1
Computer setpoint ratio
CSP BI
0
LOOPBK
DIS
Disable loopback test
Summary of Contents for S7999D1048
Page 70: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 70 ...
Page 72: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 72 ...
Page 74: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 74 ...
Page 75: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 75 65 0321 01 ...