S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
59
65-0321—01
Setpoints:
Modulation (0-500°F or 0-750 psi)
On-Off (0-500°F or 0-750 psi)
Low Fire Hold (0-500°F or 0-750 psi)
APPLICATION NOTE
Application:
Steam Pressure Load Control
Description:
On-off and modulating outputs to start/stop and adjust firing rate to maintain a control
setpoint.
M24242
FIRING RATE
MOTOR
INTERFACE
MODBUS COMMUNICATION
HONEYWELL S7810M
L1
ON–OFF
CONTROL
BURNER
CONTROL
L1
D+
+
-
+
-
R
D-
SHIELD
26
27
25
21
19
17 18
16
5
9
8
-
+
6
L2
L1
G
C
A
B
L1
L2
250 OHM
RESISTOR
STEAM
PRESSURE
SENSOR
(STD 904
SERIES)
UDC
CONTROLLER
Digital Inputs:
None
Digital Outputs:
On-Off relay
Optional: Modulation Alarm1 (ON
when at or below Modulation setpoint,
OFF when above Modulation setpoint)
Optional: Low Fire Hold Alarm2 (ON
when at or below Low Fire Hold
setpoint, OFF when above Low Fire
Hold setpoint)
Analog Inputs:
Steam pressure sensor (0-750
psi) (4-20mA)
Analog Outputs:
PID modulation (4-20mA) to control
firing rate. Modulation based on
modulation setpoint.
Application File:
steam01.nge
steam02.nge
steam03.nge
steam04.nge
steam05.nge
steam06.nge
steam07.nge
steam08.nge
Range
0–15 psi
0–15 psi
LOW FIRE
0–150 psi
0–150 psi
LOW FIRE
0–300 psi
0–300 psi
LOW FIRE
0–750 psi
0–750 psi
LOW FIRE
Summary of Contents for S7999D1048
Page 70: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 70 ...
Page 72: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 72 ...
Page 74: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 74 ...
Page 75: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 75 65 0321 01 ...