S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
65-0321—01
10
System S7999D Configuration
The S7999D can be configured to monitor all burner/boiler
systems via a System Modbus™ network. One S7999D is
designated the System S7999D (master) on the network, and
the other S7999Ds are designated as a Local S7999D (slave)
to provide system status for their respective burner/boiler
system.
Fig. 8 depicts this type of configuration. Only S7999Ds are
wired together in this configuration (using either COM port).
Only one S7999D can be configured as the System S7999D
on this Modbus™ network. This S7999D assumes the
Modbus™ master role on the selected COM port. Only the
System S7999D can view any burner/boiler system on the
network; the Local S7999D can only view its own burner/boiler
system.
Fig. 8. System Modbus™ network.
Up to 99 Local burner/boiler systems can be connected
together and displayed at the System S7999D.
A Modbus™ register interface is used in the Local S7999D to
provide status data to the System S7999D. Many of the
register addresses and definitions for the burner control,
expanded annunciator, and R7999 have the same definitions
that the S7810M specifies in its interface.
At the System S7999D a quick search for Local S7999Ds on
the System Modbus™ network can be performed. This
function is expected to be used after a new Local burner/boiler
system is attached to the System Modbus™ network. If the
quick search isn’t done, a slower, automatic search eventually
finds new Local burner/boiler systems.
R7999
FUEL AIR
RATIO CONTROL
S7830
EXPANDED
ANNUNCIATOR
RM78xx
BURNER
CONTROL
S7810M
MODBUS
S7999D
SYSTEM DISPLAY
S7999D
SYSTEM DISPLAY
CONTROLBUS
COM 1 OR
COM 2
M33564C
MASTER
SLAVE
SYSTEM MODBUS
LOCAL MODBUS
SYSTEM S7999D
LOCAL S7999D
UP TO 99
LOCAL S7999D
SYSTEMS
UDC2500
THERMAL
SHOCK
UDC2500
PID LOAD
CONTROL
UDC2500
FEED PUMP
LEVEL CONTROL
UDC2500
STACK
TEMPERATURE
UDC2500
STEAM/FUEL
FLOW
R7999
FUEL AIR
RATIO CONTROL
S7830
EXPANDED
ANNUNCIATOR
RM78xx
BURNER
CONTROL
S7810M
MODBUS
S7999D
SYSTEM DISPLAY
CONTROLBUS
SLAVE
LOCAL MODBUS
LOCAL S7999D
UDC2500
THERMAL
SHOCK
UDC2500
PID LOAD
CONTROL
UDC2500
FEED PUMP
LEVEL CONTROL
UDC2500
STACK
TEMPERATURE
UDC2500
STEAM/FUEL
FLOW
R7999
FUEL AIR
RATIO CONTROL
S7830
EXPANDED
ANNUNCIATOR
RM78xx
BURNER
CONTROL
S7810M
MODBUS
S7999D
SYSTEM DISPLAY
CONTROLBUS
SLAVE
LOCAL MODBUS
LOCAL BURNER/
BOILER SYSTEM
LOCAL BURNER/
BOILER SYSTEM
LOCAL BURNER/
BOILER SYSTEM
LOCAL S7999D
UDC2500
THERMAL
SHOCK
UDC2500
PID LOAD
CONTROL
UDC2500
FEED PUMP
LEVEL CONTROL
UDC2500
STACK
TEMPERATURE
UDC2500
STEAM/FUEL
FLOW
2
2
2
2
1
1
1
MODBUS BAUD RATE MUST BE SET FOR EITHER 9600 OR 19200.
1
ANY MODBUS BAUD RATE CAN BE USED; HOWEVER THE SELECTED BAUD RATES MUST MATCH.
2
COM 1 OR
COM 2
COM 1 OR
COM 2
COM 1 OR
COM 2
COM 1 OR
COM 2
COM 1 OR
COM 2
COM 1 OR
COM 2
Summary of Contents for S7999D1048
Page 70: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 70 ...
Page 72: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 72 ...
Page 74: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 74 ...
Page 75: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 75 65 0321 01 ...